Riello UPS Multi Power2 (MP2) 300–600 kW Modular Online UPS
The Riello UPS Multi Power2 (MP2) is a 300–600 kW modular three-phase online (double-conversion) UPS. The MP2 cabinets are built from hot-swappable 67 kW, 3U power modules and run on external batteries. The range serves data centers and critical industrial and transport loads; with BLUE (SiC) modules, online-mode efficiency is up to 98.1% in front-to-back cabinets and up to 98% in the top-ventilated VE cabinets, which accept BLUE modules only.
Key specifications at a glance
- Output power factor: 1.0 (kW = kVA)
- Topology: online, double-conversion; VFI-SS-111 (IEC 62040-3)
- Power module: 67 kW, 3U: MP2 67 PM (IGBT) or MP2 67 PM BLUE (SiC), BLUE only in VE cabinets and the top-ventilated MP2 300 PCM
- Efficiency (online mode): max 96.5% with IGBT module; max 98.1% with BLUE (SiC) module (top-ventilated MP2 600 VE: max 98%)
- Input THDi: <3%
- Parallel capability: max 6 systems, 3,600 kW in total
Applications
- Data centers and high-density critical IT environments
- Industrial loads where continuity of power is a requirement
- Critical systems in transport infrastructure
Multi Power2 (MP2) modular UPS models
| Model | Rated power | Key feature |
|---|---|---|
| MP2 300 PCM | 300 kW | integrated manual bypass, 5 module slots |
| MP2 500 PCM | 500 kW | integrated manual bypass, 8 module slots |
| MP2 600 PC0 | 600 kW | without switches, front-to-back ventilation, 9 module slots |
| MP2 600 PC0 VE | 600 kW | without switches, top ventilation, BLUE modules only |
| MP2 600 PCS VE | 600 kW | full switch set (input, bypass, manual bypass, output), top ventilation, BLUE modules only |
| MP2 600 CT4 VE | 600 kW | top ventilation, switches and internal backfeed protection device, BLUE modules only |
All cabinets are built from 67 kW modules. The front-to-back MP2 300 PCM, MP2 500 PCM and MP2 600 PC0 accept MP2 67 PM (IGBT) or MP2 67 PM BLUE (SiC) modules; the VE cabinets and the top ventilation option of the MP2 300 PCM work with BLUE modules only. Ratings below the cabinet's nominal power are set by the number of installed modules.
Technical specifications
| Parameter | Value |
|---|---|
| Cabinet nominal and bypass power | MP2 300: 300 kW; MP2 500: 500 kW; MP2 600: 600 kW (bypass power identical) |
| Module slots and modules for full power | MP2 300: 5 slots, 5 modules; MP2 500: 8 slots, 8 modules; MP2 600: 9 slots, 9 modules |
| Input rated voltage | 380 / 400 / 415 V, three-phase + neutral |
| Input voltage tolerance | 240–480 V (conditions apply) |
| Input frequency | 50 / 60 Hz; tolerance 40–72 Hz |
| Input power factor | 0.99 |
| Bypass voltage tolerance | 180 V (adjustable 180–200 V) to 264 V (adjustable 250–264 V), referred to neutral |
| Bypass frequency tolerance | ±5% (adjustable), at 50 or 60 Hz rated frequency |
| Bypass overload | 125% for 10 min; 150% for 1 min |
| Output rated voltage and frequency | 380 / 400 / 415 V, three-phase + neutral (conditions apply for wider tolerance); 50 or 60 Hz |
| Output voltage stability | ±1% |
| Dynamic stability | EN 62040-3 performance class 1, non-linear load |
| Max parallel system power (up to 6 units) | MP2 300: 1,800 kW; MP2 500: 3,000 kW; MP2 600: 3,600 kW |
| Battery and energy storage types | external; VRLA, Li-ion, supercapacitors |
| Battery arrangement (parallel systems) | separate or common battery |
| Recharging method | one-level, two-level or cyclic recharge (selectable) |
| Operating modes and features (standard) | EFFICIENCY CONTROL mode, ACTIVE ECO mode, power walk-in, backfeed detection and protection, fan monitoring, smart grid ready |
| Communication (standard) | 10-inch color touch screen, LED bar, NetMan 208C network card, configurable signals (MP2 500 and MP2 600: 10 inputs, 8 outputs; MP2 300: 5 inputs, 4 outputs), 2 free communication slots, R.E.P.O. |
| Power density | MP2 600 PC0: 600 kW in a 0.52 m² footprint; power module: 1.75 kW/dm³ |
| Ventilation | MP2 300 PCM: front to back (top ventilation optional, BLUE modules only); MP2 500 PCM and MP2 600 PC0: front to back; MP2 600 VE cabinets: front to top, BLUE modules only |
| Cable entry | MP2 300 PCM: front access, bottom (top optional); MP2 500 PCM and MP2 600 PC0: front access, top (bottom optional); MP2 600 PC0 VE and PCS VE: top or bottom; MP2 600 CT4 VE: not stated in the datasheet |
| Dimensions (W × D × H) and weight | MP2 300 PCM: 600 × 940 × 1,995 mm, 429 kg; MP2 500 PCM: 600 × 870 × 1,997 mm, 640 kg; MP2 600 PC0: 600 × 870 × 1,997 mm, 680 kg; MP2 600 PC0 VE: 1,000 × 990 × 2,000 mm, 800 kg; MP2 600 PCS VE: 1,200 × 990 × 2,000 mm, 930 kg (with the modules needed for full power); MP2 600 CT4 VE: dimensions and weight not stated in the datasheet |
| Noise level | MP2 300: <68 dBA; MP2 500: <69 dBA; MP2 600 with front-to-back ventilation: <70 dBA; MP2 600 with front-to-top ventilation: <78 dBA (±2 dBA, conditions apply) |
| Cabinet protection rating | IP20 (others on request) |
| Ambient temperature | 0–40 °C |
| Relative humidity | 5–95%, non-condensing |
| Color | RAL 9005 |
| Directives and standards | LV 2014/35/EU, EMC 2014/30/EU; safety: IEC EN 62040-1; EMC: IEC EN 62040-2; RoHS compliant |
Source: Riello UPS Multi Power2 300–500–600 kW catalog sheet (DATMP2M3T26FREN, 2026-06-16) and Riello UPS product page (November 2026). Specifications are subject to change by the manufacturer.
How to choose
Cabinet size and module count
Choose the cabinet (MP2 300, MP2 500 or MP2 600) for the final power requirement; intermediate ratings are set by the number of installed 67 kW modules. Modules are hot-swappable.
Module type: IGBT or BLUE (SiC)
With the MP2 67 PM (IGBT) module, online-mode efficiency is up to 96.5%; with the MP2 67 PM BLUE (SiC) module, up to 98.1% (up to 98% in the top-ventilated MP2 600 VE cabinets). The VE cabinets and the top ventilation option of the MP2 300 PCM work with BLUE modules only.
Switches and backfeed protection
The MP2 300 PCM and MP2 500 PCM include an integrated manual bypass; the MP2 600 PC0 and PC0 VE come without switches. The MP2 600 PCS VE has a full switch set (input, bypass, manual bypass, output), and the MP2 600 CT4 VE includes switches and an internal backfeed protection device.
Ventilation and cable entry
For front-to-back airflow, the 600 mm wide MP2 300 PCM, MP2 500 PCM and MP2 600 PC0 cabinets fit; front-to-top airflow calls for the MP2 600 VE cabinets (MP2 600 PC0 VE: 1,000 mm, MP2 600 PCS VE: 1,200 mm wide), which work with BLUE modules only. Cable entry is from the top or bottom depending on the model.
Parallel expansion and batteries
Up to 6 systems can be paralleled (up to 3,600 kW with MP2 600). All models use external batteries: VRLA, Li-ion or supercapacitors, as separate or common battery banks in parallel systems.
Related services and products
- UPS systems – other product families in this category
- UPS maintenance – preventive maintenance and service for UPS systems
- Uninterruptible power supply – system-level design around the critical load
- Industrial batteries – external battery banks for UPS systems
- Riello UPS Multi Power2-M2X
- Riello UPS Multi Power2 Scalable (M2S)
- Riello UPS NextEnergy (NXE)
Energom Electronic Kft. is an official distributor of Riello UPS. Energom handles sizing, installation, commissioning and maintenance of Multi Power2 systems, including selection of the external battery bank. Services across the Central and Eastern European region; product delivery across Europe.
FAQ
Can the Riello UPS Multi Power2 (MP2) be paralleled?
Yes. Up to 6 Riello UPS Multi Power2 (MP2) systems can operate in parallel; maximum parallel system power is 1,800 kW with MP2 300 cabinets, 3,000 kW with MP2 500 and 3,600 kW with MP2 600.
What is the difference between the MP2 67 PM and MP2 67 PM BLUE modules?
Both are 67 kW, 3U Multi Power2 power modules. The MP2 67 PM is IGBT-based, with online-mode efficiency up to 96.5%; the MP2 67 PM BLUE is SiC-based, with online-mode efficiency up to 98.1% in front-to-back cabinets and up to 98% in the top-ventilated MP2 600 VE cabinets. The VE cabinets and the top ventilation option of the MP2 300 PCM run on BLUE modules only.
What batteries does the Multi Power2 (MP2) use?
The Multi Power2 (MP2) uses external batteries; the manufacturer lists VRLA, Li-ion and supercapacitor energy storage. Parallel systems can use separate or common batteries.
What energy-saving modes does the Multi Power2 (MP2) offer?
EFFICIENCY CONTROL mode and ACTIVE ECO mode are standard on the Multi Power2 (MP2). The manufacturer's datasheet does not state an ACTIVE ECO mode efficiency.
Request a quote
For an accurate quote, include the protected load and planned expansion in kW, the required redundancy, the backup time, the ventilation and cable entry conditions on site, and whether built-in switches or backfeed protection are needed.
We respond within 24 hours on business days.