Maintenance and Service — UPS, Battery and Generator Systems
The reliability of an uninterruptible power supply system can only be sustained through regular maintenance. A postponed battery replacement or skipped inspection can cause an entire production line to stop — exactly when redundancy is no longer an option. Our maintenance services are manufacturer-independent: we service mixed infrastructure from a single partner — the Riello UPS, FIAMM, Delta Electronics and Eltek systems we distribute, and equipment from other manufacturers as well. 25+ years of service experience, in-house service team, in-house spare parts inventory. We provide this service across the Central and Eastern European region.
UPS Maintenance
Planned maintenance intervals, battery condition assessment, parameter calibration, capacitor and fan checks, firmware updates. Preventive maintenance reduces the risk of unexpected downtime and helps keep the UPS close to its design-life targets; the actual effect depends on ambient temperature, load profile and service depth. The full scope, SLA levels and urgent case handling are on the detailed UPS maintenance page.
When you need it:
- UPS not serviced for 12+ months
- manufacturer alarm or error message received
- battery warning from supervision system
- taking over a facility with unknown service history.
Battery Capacity Test
Nominal and actual battery capacity can differ significantly after 3-5 years — with no visible warning. The supervision system may still show the nominal autonomy while the real backup time is already significantly shorter. We measure the actual battery capacity (Cn, at the 10/20/100-hour rate) with a load-bank discharge test; internal resistance (Ri) measurement is a separate condition indicator. In addition: cell voltage measurement, thermal gradient analysis, lifetime estimate and scheduled replacement plan. Alongside the battery capacity, the report contains voltage and Ri data for each identifiable cell, with the limiting cells marked. Detailed process and technology-specific differences (AGM / GEL / OPzV / OPzS / LiFePO4) on the detailed battery maintenance page.
When you need it:
- battery 4+ years old
- elevated internal resistance
- thermal drift between cells
- validating bank capacity before UPS replacement
- taking over an unfamiliar system as a new operator.
Inspection and Fault Diagnosis
Condition diagnosis, root cause analysis, on-site measurement. Visual and thermal inspection (hot-spot check via thermal imaging), capacitor ESR measurement, communication interface and supervision check, alarm log evaluation, parameter readout via manufacturer diagnostic tools. The result is a written report — assessed condition, risk classification (critical / medium / low), prioritized action plan with timeline and cost estimate.
When you need it:
- no substantive service for 3+ years
- manufacturer warranty about to expire and you want to know what you're stepping into
- new owner or new operator has taken over the facility
- recurring error messages but no outage yet
- audit / due diligence.
Repair and Troubleshooting (Reactive)
Response time is set by the SLA level and the individual contract. In-house parts inventory — the most common failure components (control boards, fans, capacitors, communication modules, IGBT blocks) are typically in stock, so in many cases repair does not have to wait for parts to arrive. Full fault diagnosis using manufacturer diagnostic tools, documented repair, post-mortem report with root cause and prevention recommendation.
When you need it:
- error message or alarm in the supervision system
- outage or operational disruption
- production line issue traced back to power supply
- recurring fault never satisfactorily closed.
Urgent case? Call us directly: +36 1 459 8010. For SLA-contracted partners, response and on-site arrival times are set in the individual contract.
UPS Battery Replacement
Planned replacement at end-of-life or in case of failure. New battery bank sizing (where appropriate, on a higher capacity bank than the original design), original manufacturer battery or compatible alternative (manufacturer-independent), professional removal and environmentally compliant disposal with MET documentation, new bank installation, initial capacity test and reconfiguration in the UPS supervision. Work scheduled to a planned downtime window — for critical loads with bridging mobile UPS.
When you need it:
- battery capacity <80% nominal
- age limit (manufacturer-specified end of design life)
- cell-level failure justifying full bank replacement
- technology change (e.g. lead-acid → LiFePO4) under consideration.
UPS Retrofit
A retrofit can extend the useful life by several years and is typically less expensive than a full replacement — particularly when the topology is still appropriate and only the components have aged. Control board replacement, capacitor refresh (the most common life-limiting component), fan replacement, new battery bank, firmware update, communication module modernization (SNMP v3, BACnet IP). We quantify the expected service life and savings after the on-site survey.
When you need it:
- 8-10 year old system with parts still available
- topology and sizing still adequate, only aging components need replacement
- insufficient space for a larger new UPS.
Warranty and Post-Warranty Service
Within manufacturer warranty: for products we distribute, we handle the warranty case with the manufacturer, including factory repair, parts replacement and case management — you don't need to deal with separate manufacturer portals. Post-warranty full support: parts supply (in-house inventory + international manufacturer chain), repair, retrofit, battery replacement — even for systems no longer supported by the original manufacturer.
When you need it:
- new system, warranty service
- approaching warranty expiry (with a timely condition assessment, transition to post-warranty support is seamless)
- 8+ year old system with limited or terminated manufacturer support.
SLA-Based Maintenance Contract
Standard, Premium and 24/7 SLA levels — predefined service intervals, annual fee structure. Fault reporting, response time and on-site arrival time are set per level and per site in the individual contract. The contract includes the planned preventive maintenance (PM) schedule, reactive troubleshooting response time, parts settlement model, and alarm handling where remote monitoring is included. Exact terms — response and on-site arrival time by location, parts settlement model, hourly rate tiers — are set in the individual quotation and contract.
When you need it:
- critical operation where even one hour of outage causes significant losses
- expiring manufacturer warranty and you seek comprehensive support
- multi-site system where service coordination across locations is handled by one partner
- auditable service history requirement.
Not Sure Which Service You Need?
- UPS not serviced for 3+ years → Inspection and Fault Diagnosis
- Battery 4+ years old → Battery Capacity Test
- Error message, alarm, outage → Repair and Troubleshooting
- Warranty about to expire → SLA-Based Maintenance Contract
- 8-10 year old UPS, working but aging → UPS Retrofit