The systems are sized specifically for the standards-driven supply of rail and industrial switchgear — high reliability requirements, long lifecycle and the ability to handle breaker tripping current surges.

How to Choose a 72/110 VDC System?

The 72 and 110 VDC segment is specialized — protection and control supply for rail and heavy-industrial switchgear. Specification starts from the protection system and switchgear manufacturer requirements.

Voltage level and compatibility

72 VDC is the typical rail signaling voltage; 110 VDC is the standard for industrial switchgear protection. The voltage tolerance of the protection system and breakers (typically ±10-20%) drives the regulation range of the rectifier plant.

Inrush current and load profile

Breaker trip currents can spike to several times the nominal current within a second. The rectifier plant and battery bank must deliver this peak without interruption — peak current must be considered alongside steady-state current during sizing.

Battery technology and life

OPzS stationary cells are the traditional choice for rail and heavy-industrial systems — the manufacturer's design life for FIAMM LM (OPzS) cells is 20 years (a design figure, not a guaranteed service life; actual life depends on temperature and operating conditions). OPzV where operation without water topping-up (VRLA) is required; periodic checks (cell voltage, temperature, impedance, valves) are still required per the manufacturer's instructions. For OPzS, electrolyte level checks and water topping-up as needed are part of maintenance. LiFePO4 only if both the protection system and the rectifier plant support it.

Redundancy and dual feed

N+1 rectifiers, dual AC feeds, automatic transfer switching (ATS) is standard practice. The reliability requirement (RAMS, rail SIL) drives the redundancy level.

Monitoring and diagnostics

Cell-level voltage monitoring, ground-fault detection, communication with SCADA or station controller (Modbus, IEC 61850). The rail environment typically requires IEC 61850 or a manufacturer-specific protocol.

Lifecycle and spare-parts availability

Rail and switchgear infrastructure runs in a 20-30 year lifecycle — long-term manufacturer support and spare-parts availability are critical at procurement.

Decision guide

SituationRecommended solutionWhyNext step
Rail signaling 72 VDC system with N+1 rectifiers High reliability, long lifecycle DC power systems
Industrial switchgear protection 110 VDC system with rectifiers and battery bank sized for the trip current and the permissible voltage drop, with dual AC feeds The DC side delivers the trip current surge; dual AC feeds provide redundancy against loss of supply Design and installation
Long life, traditional design OPzS battery bank Vented, flooded, long-life cells; electrolyte level checks and water topping-up required Industrial batteries
Infrequent site access, operation without water topping-up OPzV battery bank VRLA cells, no water topping-up required; periodic checks still apply Industrial batteries

The Energom advantage

  • Rail and industrial switchgear reference projects.
  • OPzS / OPzV battery banks sized for long-lifecycle service.
  • Standards-compliant configurations compatible with protection systems.