Systems are built from hot-swappable rectifier modules of 1,000–3,050 W each (Eltek Flatpack S, Flatpack2, Delta DPR 3000) and expand by adding modules in parallel; with AGM/GEL or OPzV battery banks and remote monitoring controllers (Eltek Smartpack, Delta ORION), we size them for continuous operation in telecom and edge-IT environments.

Our Products

Eltek Flatpack2 48 V HE, 2,000–3,000 W

High-efficiency, hot-pluggable rectifier module family for the 48 VDC power supply of radio base stations, central offices, data center equipment and utility control and protection systems, with 2,000 W and 3,000 W output power and wide input voltage and temperature ranges. Manufactured by Eltek.

Output
48 VDC (default 53.5 VDC); 2,000 W / 41.7 A (48/2000 HE), 3,000 W / 62.5 A (48/3000 HE)
Efficiency
96% at nominal input voltage
Input voltage
85–300 VAC (48/2000 HE), 85–305 VAC (48/3000 HE); full power between 185–275 and 176–277 VAC respectively
Operating temperature
−40 to +75 °C; derating above +55 °C (1,200 W and 2,100 W respectively at 75 °C)
Dimensions, weight
109 × 41.5 × 327 mm (W × H × D); 1.95 kg; hot-pluggable

Eltek Flatpack S 48 V, 1,000–1,800 W (HE / SHE)

Compact, hot-pluggable rectifier module family for the 48 VDC power supply of radio base stations, distributed antenna systems and broadband and fiber-optic network equipment, with 1000 or 1,800 W output power and 217 mm depth, for space-efficient 1U and 2U power systems. Manufactured by Eltek.

Output
48 VDC (default 53.5 VDC on the 1,000 W models); 1,000 W / 20.9 A (48/1000 HE, SHE), 1,800 W / 37.5 A (1800W HE)
Efficiency
95.5% (48/1000 HE); 96% (1800W HE); above 97% (48/1000 SHE)
Input voltage
85–300 VAC (48/1000 HE), 85–305 VAC (1800W HE), 85–275 VAC (SHE); full power of the 1,000 W models between 185–250 VAC
Operating temperature
−40 to +85 °C; derating from 45 °C (48/1000 HE, 600 W at 85 °C), from 55 °C (SHE, 400 W at 85 °C)
Dimensions, weight
72 × 41.5 × 217 mm (W × H × D); 620 g (SHE), up to 850 g (HE)
Safety standard
EN/IEC/UL 62368-1 alongside IEC 60950-1 (48/1000 HE and SHE)

Eltek Rectiverter 230 V / 1,500 VA, 48–220 VDC

Hot-pluggable three-port module family for battery-backed AC and DC loads in telecom, power utility, railway and industrial facilities, combining rectifier, inverter and source transfer functions, for 48, 110 or 220 VDC battery systems, with a 1,500 VA AC output and parallel operation. Manufactured by Eltek.

Output
AC: 1,200 W (1,500 VA), 200–240 VAC, 2,000 VA for less than 15 s; DC: 48, 110 or 220 V, max 1,200 W (25 / 11.11 / 5.56 A); AC load has priority
Efficiency
>96% in grid mode; >94% in inverter mode (110 V module: >95%)
Input voltage
AC: 185–275 VAC; DC: 45–58 V (48 V), 102–145 V (110 V), 204–290 V (220 V)
Operating temperature
−40 to +75 °C
Dimensions, weight
109 × 41.5 × 327 mm (W × H × D); 1.95 kg; hot-pluggable
Parallel capability
scalable in parallel power cores to single-phase, three-phase or redundant systems

Eltek Smartpack controllers (Smartpack2 Touch / Smartpack S / Smartpack R)

Controller family for monitoring and controlling Eltek DC power systems: the touchscreen Smartpack2 Touch, the compact Smartpack S and the Smartpack R that replaces first-generation Smartpack units, with Ethernet and serial interfaces and SNMP and Modbus integration for network management systems. Manufactured by Eltek.

Interfaces
Smartpack2 Touch: 2 × CAN, 2 × Ethernet, 2 × USB host, RS-232, RS-485; Smartpack S: Ethernet, RS-232, RS-485; Smartpack R: CAN, Ethernet, RS-232, RS-485, USB
Protocols
SNMP v1/v2c/v3, Modbus TCP/RTU slave (Smartpack2 Touch, Smartpack S)
Display
4.4″ color touchscreen (Smartpack2 Touch); 2.2″ color TFT (Smartpack S)
Protection rating
IP22 (Smartpack2 Touch); IP20 (Smartpack S)
Operating temperature
−20 to +65 °C
Supply voltage
20–420 VDC (Smartpack2 Touch); 10–75 VDC (Smartpack S)

Delta DPR 3000 EnergE (DPR 3000B / DPR 3000E) 3,000–3,050 W

Single-phase, hot-pluggable, fan-cooled rectifier modules for the 48 VDC power systems of network base stations, fixed-line networks and data communications equipment, with 3,000 W (DPR 3000B) and 3,050 W (DPR 3000E) output power, in a compact 84 mm wide format. Manufactured by Delta Electronics.

Output
−43 to −58 VDC adjustable (default −54.0 VDC); max 3,000 W / 60 A (3000B), max 3,050 W / 63.5 A (3000E)
Peak efficiency
96.2% (DPR 3000B); 98.0% (DPR 3000E)
Input voltage
90–300 VAC, derating at 176 VAC or below (3000B); 80–300 VAC, derating below 180 VAC (3000E)
Operating temperature
−40 to +75 °C; derating above +55 °C
Dimensions, weight
84 × 41 × 265 mm (W × H × D); 1.3 kg (3000B), 1.4 kg (3000E)

Delta ORION controllers (ORION E / ORION ID:E1 / ORION ID:F1)

Modular system controller family for monitoring telecom power systems, multi-device sites and hybrid and renewable energy sites, with remote monitoring over Gigabit Ethernet and serial links, battery supervision, automatic battery testing and programmable logic controller (PLC) functions. Manufactured by Delta Electronics.

Supply voltage
18–75 V DC (ORION E, ORION ID:E1); 18–60 V DC (ORION ID:F1); max 0.8 A
Interfaces
Gigabit Ethernet, 2 × RS485, 1 × RS232, 1 × USB host; ORION ID:F1 also 1 × CAN (IMBUS)
Protocols
SNMP, Modbus, MQTT, HTTP-API; Syslog (ORION E, ORION ID:E1)
Operating temperature
−40 to +70 °C
Safety standard
IEC/EN/UL 62368-1
Dimensions, weight
83.4 × 40.0 × 205.1 mm, 0.5 kg (E, ID:E1); 83.4 × 40.0 × 203.9 mm, 0.46 kg (ID:F1)

How to Choose a 48 VDC System?

For telecom and edge IT, -48 VDC is the industry standard. Choosing the right DC plant is a combination of load, autonomy, redundancy and monitoring.

Load and scalability

Current draw of the base station or switching node + 25-30% headroom for growth. With a modular rectifier shelf, capacity can be expanded without downtime — sizing the cabinet and battery footprint to the planned end-state pays off.

Redundancy and battery autonomy

N+1 rectifier redundancy and 2-8 hour battery autonomy is the typical configuration. The actual autonomy is driven by the site's grid outage statistics and maintenance access time.

Battery technology

AGM is the general telecom choice, with a compact footprint. OPzV where longer life and deep DOD are required. LiFePO4 for high-temperature outdoor cabinets and sites with infrequent maintenance access.

Communication and monitoring

SNMP, Modbus, dry-contact alarms, optionally the TL1 telecom protocol. Integration into the site NMS and alarm handling is part of the procurement scope.

Operating environment

Indoor switching room, outdoor shelter, pole-mounted cabinet — temperature, IP rating and cooling demand affect both rectifier and battery selection. Above 35 °C operating temperature, dedicated chemistry and life expectancy assessment are required.

Lifecycle service

Periodic capacity testing (typically annual) is the leading indicator of network outage risk. The monitoring and maintenance SLA should be locked in at procurement.

Decision guide

SituationRecommended solutionWhyNext step
Base station, switching center Modular -48 VDC system with N+1 rectifiers Modules can be added and replaced during operation DC power systems
General telecom site AGM battery bank Compact footprint Industrial batteries
Longer life, deep discharge OPzV battery bank Longer life at deep depth of discharge (DOD) Industrial batteries
Existing site system Capacity testing and replacement planning Capacity is the leading indicator of outage risk Maintenance and service

The Energom advantage

  • Telecom and edge-IT deployment experience — from base stations to switching centers.
  • In-house stock for rapid battery and rectifier replacement.
  • Capacity testing and predictive replacement planning for installed systems.

Request a Custom Quote

We design a system sized to the site's load profile and outage window.

Request a Quote Request a Callback