Key specifications at a glance

  • Output: 48 VDC (default 53.5 VDC); 2000 W / 41.7 A (48/2000 HE), 3000 W / 62.5 A (48/3000 HE)
  • Efficiency: 96% at nominal input voltage
  • Input voltage: 85–300 VAC (48/2000 HE), 85–305 VAC (48/3000 HE); full power between 185–275 and 176–277 VAC respectively at 45–66 Hz (48/2000 HE: max 1,000 W on a 230 VAC, 16⅔ Hz supply)
  • Operating temperature: −40 to +75 °C; derating above +55 °C (1200 W and 2100 W respectively at 75 °C)
  • Dimensions, weight: 109 × 41.5 × 327 mm (W × H × D); 1.95 kg; hot-pluggable

Applications

  • Mobile and wireless networks: radio base stations, cell sites, mobile switching centers, microwave links, broadband infrastructure.
  • Fixed telecom and data centers: central offices, telephony servers, switches, fiber-optic networks, data center equipment.
  • Power utilities: battery-backed DC power for SCADA, utility control and protection systems.
  • Marine power systems (48V/2000W HE).

Flatpack2 48V HE models: 48 V rectifier modules

Flatpack2 48V HE models: 48 V rectifier modules
Model (part number) Rated output Key difference
Flatpack2 48V/2000W HE (241115.105) 2,000 W / 41.7 A AC and DC input, including low-frequency (15–18.5 Hz) AC operation
Flatpack2 48V/3000W HE (241119.105) 3,000 W / 62.5 A AC input only, highest output on the same mechanical platform

Technical specifications

Technical specifications
Parameter 48V/2000W HE 48V/3000W HE
Part number 241115.105 241119.105
Nominal output voltage 48 VDC, default 53.5 VDC 48 VDC, default 53.5 VDC
Adjustable output range 43.5–57.6 VDC 43.2–58 VDC (upper limit 57.6 VDC up to hardware revision 5)
Rated output power, current 2,000 W / 41.7 A 3,000 W / 62.5 A
Output power at 85 VAC input 850 W 1,380 W
Output on a 230 VAC, 16⅔ Hz supply max 1,000 W not applicable (45–66 Hz only)
Input voltage 85–300 VAC 85–305 VAC
Nominal input range (full power) 185–275 VAC or 185–275 VDC 176–277 VAC
DC input, full input range 85–275 VDC none (AC input only)
Input frequency 45–66 Hz, 15–18.5 Hz or DC 45–66 Hz
Input current max 11.6 A RMS max 19.2 A RMS
Efficiency 96% at nominal input voltage 96% at nominal input voltage
Power density not stated max 33 W/in³
Operating temperature −40 to +75 °C; derating above +55 °C, 1,200 W at 75 °C −40 to +75 °C; derating above +55 °C, 2,100 W at 75 °C
Overtemperature shutdown not stated shuts down at +95 °C after derating to approx. 1,000 W (from hardware revision 6)
Protection integrated fuses, transient suppression, short-circuit protection, overvoltage shutdown, thermal protection; inrush-current limiting for hot-plug insertion same
Communication, indications CAN communication to the system controller; status LEDs (normal, warning, alarm) same
Dimensions (W × H × D) 109 × 41.5 × 327 mm 109 × 41.5 × 327 mm
Weight 1.95 kg 1.95 kg
Marine certification DNVGL-CG-0339 not stated

Source: Eltek manufacturer product page (Delta EMEA), November 2026. Specifications are subject to change by the manufacturer.

How to choose

Power demand and module count

Both models share the same 109 × 41.5 × 327 mm mechanical platform and deliver 2,000 W or 3,000 W per module. The module count follows from the 48 V load, the battery charging current and the redundancy target (for example N+1); the 3,000 W model delivers the same power from fewer module positions.

Supply type: AC, DC or low-frequency grid supply

Where the site provides a DC supply (185–275 VDC nominal, 85–275 VDC full range) or a 15–18.5 Hz network, the 48V/2000W HE is the model to specify; from a 230 VAC, 16⅔ Hz supply it delivers up to 1,000 W. The 48V/3000W HE runs from 45–66 Hz AC input only.

Weak or unstable grid supply

On a 45–66 Hz supply, the 2,000 W model delivers full power between 185 and 275 VAC, the 3,000 W model between 176 and 277 VAC. At 85 VAC input, output drops to 850 W and 1,380 W respectively, so module count at low-voltage sites should be checked against these figures.

High ambient temperature

Both models derate above +55 °C: at 75 °C the 2,000 W model delivers 1,200 W and the 3,000 W model 2,100 W. In outdoor cabinets or unconditioned rooms, size the system for the highest expected internal temperature.

Marine applications

For marine power systems, the 48V/2000W HE carries DNVGL-CG-0339 certification; the manufacturer does not state this certification for the 3,000 W model.

Related services and products

Energom Electronic Kft. is an official distributor of Eltek. Services across the Central and Eastern European region; product delivery across Europe. Energom sizes Flatpack2 48V HE modules as part of a complete 48 VDC power system, covering module count, redundancy, battery bank and monitoring together, and handles installation, commissioning and scheduled maintenance.

FAQ

Can the Flatpack2 48V HE run from a DC input?

In the Eltek Flatpack2 48V HE range, only the 48V/2000W HE runs from DC input: its nominal input range is 185–275 VAC or 185–275 VDC, and its full DC input range is 85–275 VDC. The 48V/3000W HE runs from 45–66 Hz AC input only.

How much output does the Flatpack2 48V HE deliver at low AC input voltage?

At 85 VAC input, the Eltek Flatpack2 48V/2000W HE delivers 850 W and the 48V/3000W HE delivers 1,380 W. On a 45–66 Hz supply, full power is available between 185–275 VAC on the 2,000 W model and 176–277 VAC on the 3,000 W model; from a 230 VAC, 16⅔ Hz supply, the 48V/2000W HE delivers max 1,000 W.

How does the Flatpack2 48V HE behave at high temperatures?

The Eltek Flatpack2 48V HE operates from −40 to +75 °C, with derating above +55 °C: at 75 °C the 2,000 W model delivers 1,200 W and the 3,000 W model 2,100 W. From hardware revision 6, the 48V/3000W HE derates to approx. 1,000 W and then shuts down at +95 °C.

Can the Flatpack2 48V HE be used in marine applications?

The Eltek Flatpack2 48V/2000W HE is certified to DNVGL-CG-0339 and is listed by the manufacturer for marine power systems. The manufacturer does not state this certification for the 3,000 W model.

What is the difference between the Flatpack2 48V/2000W HE and 3000W HE?

The Eltek Flatpack2 48V/2000W HE delivers 2,000 W / 41.7 A and runs from AC or DC input as well as from 15–18.5 Hz networks (max 1,000 W at 230 VAC, 16⅔ Hz). The 48V/3000W HE delivers 3,000 W / 62.5 A and runs from 45–66 Hz AC input only. Both models measure 109 × 41.5 × 327 mm and weigh 1.95 kg.

How is the Flatpack2 48V HE monitored?

Each Eltek Flatpack2 48V HE module communicates with the power system controller over CAN and shows normal operation, warning and alarm states on status LEDs.

Request a quote

When requesting a quote, include the 48 V load, the redundancy target, the supply type (AC, DC or low-frequency grid supply), site temperature conditions and the required battery backup time.

Request a Quote

We respond within 24 hours on business days.

Request a Callback