Key specifications at a glance

  • Output: 48 VDC (default 53.5 VDC on the 1000 W models); 1000 W / 20.9 A (48/1000 HE, SHE), 1800 W / 37.5 A (1800W HE)
  • Efficiency: 95.5% (48/1000 HE); 96% (1800W HE); above 97% (48/1000 SHE)
  • Input voltage: 85–300 VAC (48/1000 HE), 85–305 VAC (1800W HE), 85–275 VAC (SHE); full power of the 1000 W models between 185–250 VAC at 45–66 Hz (48/1000 HE: max 450 W at 16⅔ Hz)
  • Operating temperature: −40 to +85 °C; derating from 45 °C (48/1000 HE, 600 W at 85 °C), from 55 °C (SHE, 400 W at 85 °C)
  • Dimensions, weight: 72 × 41.5 × 217 mm (W × H × D); 620 g (SHE), up to 850 g (HE)
  • Safety standard: EN/IEC 62368-1 alongside IEC 60950-1 (48/1000 HE and SHE)

Applications

  • Mobile and wireless networks: radio base stations, cell sites, LTE/4G, distributed antenna systems.
  • Fixed telecommunications: telephony servers, switches, fiber-optic (FTTx), cable and broadband systems.
  • Microwave and access networks.
  • Rail and marine infrastructure (48/1000 SHE).

Flatpack S 48V models: compact 48 V rectifier modules

Flatpack S 48V models: compact 48 V rectifier modules
Model (part number) Rated output Key difference
Flatpack S 48/1000 HE (241122.105) 1,000 W / 20.9 A AC or DC input, low-frequency AC operation; 95.5% efficiency
Flatpack S 48/1000 SHE (241122.106) 1,000 W / 20.9 A efficiency above 97%, 620 g, AC input only
Flatpack S 48V 1800W HE 1,800 W / 37.5 A highest output in the same 72 × 41.5 × 217 mm housing; availability confirmed at the quotation stage

Technical specifications

Technical specifications
Parameter 48/1000 HE 48/1000 SHE 1800W HE
Rated output power, current 1,000 W at nominal input; max 20.9 A at output voltages below 48 VDC 1,000 W at nominal input; max 20.9 A at output voltages below 48 VDC 1,800 W / 37.5 A
Default output voltage 53.5 VDC 53.5 VDC not stated
Adjustable output voltage 43.5–57.6 VDC 42–57.6 VDC 43.5–57.6 VDC
Efficiency 95.5% above 97% 96%
Input voltage (AC) 85–300 VAC 85–275 VAC 85–305 VAC
Nominal input range (full power) 185–250 VAC or 185–250 VDC 185–250 VAC not stated
DC input, operating range 85–250 VDC none (AC input only) 85–250 VDC
Input frequency 45–66 Hz, 15–18.5 Hz or DC 45–66 Hz 45–66 Hz
Input current (nominal input, full load) max 5.9 A RMS max 5.9 A RMS max 9.9 A RMS
Power factor > 0.99 at 50% load or higher > 0.99 at full load > 0.99 at 50% load or higher
Output power at 85 VAC input 420 W 420 W not stated
Output on low-frequency supply 415 W at 15 Hz, 450 W at 16⅔ Hz not applicable (45–66 Hz only) not stated
Output performance current sharing within ±5%; static regulation ±0.5%; ripple < 150 mVpp current sharing within ±5%; static regulation ±0.5%; ripple < 150 mVpp not stated
Hold-up time not stated > 10 ms at 950 W output with output voltage above 40 VDC not stated
Operating temperature −40 to +85 °C; derating from 45 °C, 600 W at 85 °C −40 to +85 °C; derating from 55 °C, 400 W at 85 °C −40 to +85 °C; derating not stated
Storage temperature −40 to +85 °C not stated −40 to +85 °C
Relative humidity 5–95% RH, non-condensing 5–95% RH, non-condensing not stated
Altitude max 2,000 m not stated not stated
Power density not stated 26 W/in³ not stated
Dimensions (W × H × D) 72 × 41.5 × 217 mm 72 × 41.5 × 217 mm 72 × 41.5 × 217 mm
Weight max 850 g 620 g max 850 g
Protection, monitoring OR-ing FET on the output; short-circuit, overtemperature and overvoltage protection; alarm, warning and CAN bus status monitoring; voltage and power keying same OR-ing protection on the output; voltage and power keying; hot-pluggable
System compatibility not stated fits existing 1U and 2U Flatpack S power cores with Smartpack S control, battery and load distribution not stated
Compliance EN/IEC 62368-1, IEC 60950-1, EN/IEC 61000 series, EN 50121, ETSI EN 300 386, RoHS, WEEE EN/IEC 62368-1, IEC 60950-1, EN/IEC 61000 series, ETSI EN 300 386, EN 50121, DNV-CG-0339, RoHS, WEEE not stated

Source: Eltek manufacturer product pages (Delta EMEA and Delta global), November 2026. Specifications are subject to change by the manufacturer.

How to choose

Power per module

The 1,000 W models deliver 20.9 A and the 1800W HE delivers 37.5 A from the same 72 × 41.5 × 217 mm housing. For larger 48 V loads, the 1,800 W model needs fewer module positions; module count follows from the load, the battery charging current and the redundancy target. Availability of the 1800W HE is confirmed at the quotation stage.

Efficiency and weight

The 48/1000 SHE reaches above 97% efficiency and weighs 620 g; the 48/1000 HE is rated at 95.5% and the 1800W HE at 96%. On sites running around the clock, the efficiency gap shows up in heat load and energy use.

Supply type: AC, DC or low-frequency grid supply

For a DC supply, specify the 48/1000 HE or the 1800W HE (both 85–250 VDC operating range); the SHE accepts AC input only. The manufacturer states 15–18.5 Hz operation for the 48/1000 HE only, delivering 415 W at 15 Hz and 450 W at 16⅔ Hz.

High ambient temperature

The operating range is −40 to +85 °C. The 48/1000 HE derates from 45 °C (600 W at 85 °C) and the SHE from 55 °C (400 W at 85 °C). In outdoor cabinets, size the module count for the highest expected internal temperature.

Expanding an existing Flatpack S system

According to the manufacturer, the 48/1000 SHE fits existing 1U and 2U Flatpack S power cores with Smartpack S control, battery and load distribution. For rail and marine infrastructure, the SHE compliance list includes DNV-CG-0339 alongside EN 50121.

Related services and products

Energom Electronic Kft. is an official distributor of Eltek. Services across the Central and Eastern European region; product delivery across Europe. Energom sizes Flatpack S modules together with the complete 48 VDC power system: module count, redundancy, battery bank and monitoring. Energom also handles new installations, expansion of existing power cores, commissioning and maintenance.

FAQ

Can the Flatpack S 48V run from a DC input?

The Eltek Flatpack S 48/1000 HE and 1800W HE also run from a DC input with an 85–250 VDC operating range; the nominal input range of the 48/1000 HE is 185–250 VAC or 185–250 VDC. The 48/1000 SHE accepts AC input only.

What is the difference between the Flatpack S HE and SHE?

The Eltek Flatpack S 48/1000 SHE reaches above 97% efficiency, accepts AC input only, derates from 55 °C and weighs 620 g. The 48/1000 HE is rated at 95.5% efficiency, runs from AC or DC input, derates from 45 °C and weighs max 850 g. Both deliver 1,000 W in a 72 × 41.5 × 217 mm housing.

Can the Flatpack S 48/1000 SHE be added to an existing system?

According to the manufacturer, the 48/1000 SHE fits existing 1U and 2U Flatpack S power cores with Smartpack S control, battery and load distribution.

What is the operating temperature range of the Flatpack S 48V?

Flatpack S 48V modules operate from −40 to +85 °C. The 48/1000 HE derates from 45 °C and delivers 600 W at 85 °C; the 48/1000 SHE derates from 55 °C and delivers 400 W at 85 °C.

Which safety standard does the Flatpack S 48V meet?

The compliance list of the Flatpack S 48/1000 HE and SHE includes the EN/IEC 62368-1 and IEC 60950-1 safety standards, plus the EN/IEC 61000 series, EN 50121 and ETSI EN 300 386. The manufacturer does not state a standard for the 1800W HE.

Request a quote

When requesting a quote, include the 48 V load, the redundancy target, the supply type, the available mounting height (1U or 2U), site temperature conditions and the required battery backup time.

Request a Quote

We respond within 24 hours on business days.

Request a Callback