Eltek Smartpack DC Power System Controllers
The Eltek Smartpack is a controller family for monitoring and controlling DC power systems, serving as the DC power system controller in Eltek rectifier systems. The family comprises the touchscreen Smartpack2 Touch, the compact Smartpack S and the Smartpack R, which replaces first-generation Smartpack units, with Ethernet and serial interfaces, SNMP and Modbus integration for network management systems and a −20 to +65 °C operating range.
Key specifications at a glance
- Interfaces: Smartpack2 Touch: 2 × CAN, 2 × Ethernet, 2 × USB host, RS-232, RS-485; Smartpack S: Ethernet, RS-232, RS-485; Smartpack R: CAN, Ethernet, RS-232, RS-485, USB
- Protocols: SNMP v1/v2c/v3, Modbus TCP/RTU slave (Smartpack2 Touch, Smartpack S, Smartpack R)
- Display: 4.4-inch color touchscreen (Smartpack2 Touch); 2.2-inch color TFT (Smartpack S)
- Protection rating: IP22 (Smartpack2 Touch); IP20 (Smartpack S)
- Operating temperature: −20 to +65 °C
- Supply voltage: 20–420 VDC (Smartpack2 Touch); 10–75 VDC (Smartpack S, Smartpack R)
Applications
- Control and monitoring of small to medium telecom and industrial DC power systems (Smartpack S).
- Space-constrained installations: 1U high, 265 mm deep, 2–3 kW Flatpack S systems (Smartpack S).
- Retrofitting existing mid-range Eltek power systems from 2005–2018 (Smartpack R).
- Hybrid sites: generator, solar and wind charger control (Smartpack2 Touch, Smartpack R).
- Telecom site monitoring including third-party equipment through Modbus RTU master (Smartpack R).
Smartpack controller models
| Model | Supply voltage | Distinguishing feature |
|---|---|---|
| Smartpack2 Touch | 20–420 VDC | 4.4-inch color touchscreen, 2 × CAN, 2 × Ethernet; distributed control |
| Smartpack S | 10–75 VDC | 2.2-inch color TFT, compact design for Flatpack S systems |
| Smartpack R | 10–75 VDC | retrofit replacement for first-generation Smartpack 1, 1U |
DC power system controller specifications
| Parameter | Smartpack2 Touch | Smartpack S | Smartpack R |
|---|---|---|---|
| Supply voltage | 20–420 VDC | 10–75 VDC | 10–75 VDC |
| Power consumption | 5.4 W | 3.1 W | 3 W |
| Display | 4.4-inch color touchscreen, 480 × RGB × 272 | 2.2-inch color TFT, QVGA, 32k colors | not stated |
| Interfaces | 2 × CAN, 2 × Ethernet, 2 × USB host, RS-232, RS-485 | Ethernet, RS-232, RS-485 | CAN, Ethernet, RS-232, RS-485, USB |
| Remote monitoring protocols | SNMP v1/v2c/v3, Modbus TCP/RTU slave | SNMP v1/v2c/v3, Modbus TCP/RTU slave | SNMP v1/v2c/v3, Modbus TCP/RTU slave; Modbus RTU master for data collection from third-party equipment (e.g. smart meters, lithium-ion batteries) |
| Network services | IPv4/IPv6, DHCP/DHCPv6, SNTP, SMTP, RADIUS, FTP/FTPS, HTTP/HTTPS web interface | same as Smartpack2 Touch | same as Smartpack2 Touch |
| Relay outputs | 6 programmable, potential-free changeover contact (Form C, NO-C-NC), max 75 V | 6 programmable, potential-free changeover contact (Form C, NO-C-NC), max 75 V | max 75 V / 2 A / 60 W |
| Configurable inputs | 6 programmable multi-purpose inputs (digital or analog signal); analog functions: NTC temperature sensing, ±0–10 V, 4–20 mA | 6 programmable multi-purpose inputs (digital or analog signal); analog functions: NTC temperature sensing, ±0–10 V, 4–20 mA | 6 configurable (digital or analog voltage, 0–75 V); NTC temperature sensing |
| Measurement inputs | voltage: 1 or 3; current: 1 or 2; battery midpoint: 2 | voltage: 1; current: 1; midpoint: 2 | voltage: 1; current: 1; midpoint: 4 |
| LVD control | battery LVD (LVBD) and 2 load LVDs (LVLD) | 1 battery and 1 load LVD | 1 battery and 2 load LVDs |
| Battery monitoring | temperature compensation, midpoint and block symmetry measurement, automatic and interval boost charging, equalize charging, battery test (SoH), SoC monitoring (% or Ah), temperature-based lifetime prediction | same as Smartpack2 Touch | same as Smartpack2 Touch |
| Hybrid functions | generator start and stop by SoC, voltage or schedule; solar and wind charger priority; fuel tank level monitoring | not stated | same as Smartpack2 Touch |
| Supervised equipment | Eltek rectifiers, Rectiverter modules, solar and wind chargers, CAN nodes | Eltek rectifiers, Rectiverter modules | Eltek power modules including Rectiverter modules, solar and wind chargers, CAN nodes |
| Backward compatibility | not stated | not stated | same dimensions, connections and functions as first-generation Smartpack (Smartpack 1, 2005–2018) controllers |
| Dimensions (W × H × D) | 174 × 78 × 41 mm | 72.2 × 43 × 220.7 mm | 109 × 44 (1U) × 156 mm |
| Protection rating | IP22 | IP20 | not stated |
| Operating temperature | −20 to +65 °C | −20 to +65 °C | −20 to +65 °C |
| Storage temperature | −40 to +85 °C | −40 to +70 °C | −40 to +70 °C |
| Marine certification | IEC 60945, DNVGL CG-0339 | DNV 2.4 (part no. 242100.410M only) | not stated |
Source: Eltek manufacturer product page (Delta Electronics global site: Smartpack2 Touch, Smartpack S, Smartpack R), November 2026. Specifications are subject to change by the manufacturer.
How to choose
| Situation | Recommended model | Why |
|---|---|---|
| Distributed-control system with local touchscreen operation | Smartpack2 Touch | 4.4-inch touchscreen, 2 × CAN, 2 × Ethernet, 20–420 VDC supply |
| Compact 1U Flatpack S system | Smartpack S | 2.2-inch color TFT, 10–75 VDC, small footprint |
| Replacing a first-generation Smartpack controller | Smartpack R | same dimensions, connections and functions as Smartpack 1 controllers |
| Hybrid site with a generator, solar or wind charger | Smartpack2 Touch or Smartpack R | hybrid functions: generator control, charger priority, fuel tank level monitoring |
System voltage
The Smartpack2 Touch runs on 20–420 VDC, the Smartpack S and Smartpack R on 10–75 VDC; start from the voltage of the DC system to be controlled.
Monitoring integration
All three models connect to a network management system over SNMP v1/v2c/v3 and Modbus TCP/RTU slave, with an HTTP/HTTPS web interface. For collecting data from third-party equipment, use the Modbus RTU master function of the Smartpack R.
Batteries and load disconnect
The number of LVD outputs differs by model: the Smartpack S handles 1 battery and 1 load LVD, the Smartpack R 1 battery and 2 load LVDs. For battery midpoint measurement, the Smartpack R provides 4 inputs, the other two models 2.
Related services and products
- 48 VDC systems – rectifiers and controllers in this category
- Monitoring and optimization – remote monitoring and alarm handling
- Battery maintenance – maintenance of the supervised battery bank
- DC power systems – 48 VDC solutions for telecom sites
- Eltek Flatpack2 48 V HE rectifiers
- Eltek Flatpack S 48 V rectifiers
- Eltek Rectiverter
Energom Electronic Kft. is an official distributor of Eltek. Services across the Central and Eastern European region; product delivery across Europe. For Smartpack controllers, Energom handles model selection, integration into existing systems or controller replacement, connection to your monitoring system, commissioning and maintenance.
FAQ
What replaces a first-generation Eltek Smartpack (Smartpack 1) controller?
The Smartpack R: according to the manufacturer, it has the same dimensions, connections and functions as first-generation Smartpack (Smartpack 1, 2005–2018) controllers. It runs on 10–75 VDC in a 1U format.
Which protocols connect the Smartpack to a monitoring system?
All three Eltek Smartpack models support SNMP v1/v2c/v3 and Modbus TCP/RTU slave, plus an HTTP/HTTPS web interface, SMTP and RADIUS. As a Modbus RTU master, the Smartpack R also collects data from third-party equipment.
Which Smartpack controller suits a hybrid site?
The hybrid functions of the Smartpack2 Touch and Smartpack R cover generator start and stop by SoC, voltage or schedule, solar and wind charger priority, and fuel tank level monitoring.
What is the operating temperature range of Smartpack controllers?
All three Eltek Smartpack models operate from −20 to +65 °C. Storage temperature is −40 to +85 °C (Smartpack2 Touch) or −40 to +70 °C (Smartpack S, Smartpack R).
Request a quote
When requesting a quote, include the DC system voltage and type, for a retrofit the controller to be replaced, your monitoring system protocol, the number of LVDs and battery strings, and any hybrid site equipment.
We respond within 24 hours on business days.