Eltek Rectiverter 1,500 VA 48–220 VDC Rectifier-Inverter Module
The Eltek Rectiverter is a hot-pluggable three-port module range with a 230 VAC, 1,500 VA output, combining rectifier, inverter and automatic source transfer for 48, 110 or 220 VDC battery systems. The 48/1200 and 48/150 models supply DC and AC loads at the same time; at full AC load, the DC output of the 1,200 W model is limited to 800 W, and the 48/0 version has no DC output.
Key specifications at a glance
- Output: AC: 1200 W (1500 VA), 200–240 VAC, 2000 VA for less than 15 s; DC: 48, 110 or 220 V, max 1200 W (25 / 11.11 / 5.56 A), max 800 W at full AC load; AC load has priority
- Efficiency: >96% in grid mode; >94% in inverter mode (110 V module: >95%)
- Input voltage: AC: 185–275 VAC; DC: 45–58 V (48 V), 102–145 V (110 V), 204–290 V (220 V)
- Operating temperature: −40 to +75 °C (220 V module: derating above +55 °C)
- Dimensions, weight: 109 × 41.5 × 327 mm (W × H × D); 1.95 kg; hot-pluggable
- Parallel capability: scalable in parallel power cores to single-phase, three-phase or redundant systems
Applications
- Telecommunications: backed-up AC and DC power for LTE/4G networks, distributed antenna systems, broadband infrastructure (48 V).
- Power utilities: switch tripping, SCADA, switchgear, substations, power-generation control and protection.
- Railway and metro infrastructure: signaling, communications, control centers, converter stations.
- Critical industrial power with simultaneous AC and 110 or 220 VDC supply.
- Emergency lighting (220 V).
Rectiverter models: 48 V rectifier module and inverter in one, plus 110 V and 220 V versions
| Model (part number) | Rated output | Key difference |
|---|---|---|
| Rectiverter 230/1500 48/1200 (241123.100) | 1,500 VA AC + max 1,200 W / 25 A DC, 48 V | for 48 V battery systems |
| Rectiverter 230/1500 48/150 (241123.101) | 1,500 VA AC + 150 W / 3.13 A DC, 48 V | small DC output, primarily AC supply |
| Rectiverter 230/1500 48/0 (241123.102) | 1,500 VA AC, 48 V | no DC output (port remains bidirectional) |
| Rectiverter 230/1500 110/1200 (241123.130) | 1,500 VA AC + max 1,200 W / 11.11 A DC, 110 V | for 110 V battery systems; inverter efficiency > 95% |
| Rectiverter 230/1500 110/150 (241123.131) | 1,500 VA AC + 150 W / 1.38 A DC, 110 V | small DC output |
| Rectiverter 230/1500 110/0 (241123.132) | 1,500 VA AC, 110 V | no DC output |
| Rectiverter 230/1500 220/1200 (241123.140) | 1,500 VA AC + max 1,200 W / 5.56 A DC, 220 V | for 220 V battery systems |
| Rectiverter 230/1500 220/150 (241123.141) | 1,500 VA AC + 150 W / 0.69 A DC, 220 V | small DC output |
| Rectiverter 230/1500 220/0 (241123.142) | 1,500 VA AC, 220 V | no DC output |
Technical specifications
| Parameter | 48 V modules | 110 V modules | 220 V modules |
|---|---|---|---|
| AC output | 1,200 W (1,500 VA), 200–240 VAC; 2,000 VA for less than 15 s | same | same |
| Default inverter frequency | 50 Hz, adaptive | 50 Hz, adaptive | 50 Hz, adaptive |
| Optional output frequency | 94–106 Hz or 74–76 Hz, depending on hardware and firmware revision | 94–106 Hz, firmware 1.20/1.20 or later | 94–106 Hz, firmware 1.10/1.10 or later |
| AC output THD | < 1.5% with a resistive load | < 1.5% with a resistive load | < 1.5% with a resistive load |
| DC output (1,200 W model) | max 1,200 W / 25 A | max 1,200 W / 11.11 A | max 1,200 W / 5.56 A |
| DC output (150 W model) | 150 W / 3.13 A at output voltages of 48 VDC or lower | 150 W / 1.38 A at output voltages of 108 VDC or lower | 150 W / 0.69 A at output voltages of 216 VDC or lower |
| DC output at full 230 VAC load (1,200 W model, nominal input) | max 800 W (16.6 A) | max 800 W (7.4 A) | max 800 W |
| Adjustable DC output voltage | 43–58 VDC, default 53.5 VDC | 97–145 VDC, default 122.5 VDC | 194–290 VDC, default 245 VDC |
| AC input | 185–275 VAC; disconnect at 170 VAC | same | same |
| DC input | 45–58 V | 102–145 V | 204–290 V |
| Extended DC input range | 40–45 VDC | 90–102 VDC | 180–204 VDC |
| Maximum battery current | 32 A, 45 A for 15 s | 12.5 A, 18 A for 15 s | 6.67 A, 9 A for 15 s |
| Efficiency, grid mode | >96% | >96% | >96% |
| Efficiency, inverter mode | >94% | >95% | >94% |
| Operating temperature | −40 to +75 °C; derating not stated | −40 to +75 °C; derating not stated | −40 to +75 °C; derating above +55 °C, from 1,200 W to 480 W at +75 °C |
| Relative humidity | 5–95% RH, non-condensing | 5–95% RH, non-condensing | 5–95% RH, non-condensing |
| MTBF | 260,000 hours at +25 °C | 260,000 hours at +25 °C | not stated |
| Protection | fuses, transient suppression, output overvoltage shutdown, short-circuit protection, DC reverse-polarity protection | same, plus OR-ing FET | same as the 48 V modules |
| AC-port surge protection | not stated | external AC-port surge protection is required to meet the 4 kV surge requirement | external AC-port surge protection is required to meet the 4 kV surge requirement |
| Communication | CAN and synchronization buses: adaptive frequency, parallel load sharing, alarms, system-level control | same | same |
| Dimensions (W × H × D), weight | 109 × 41.5 × 327 mm; 1.95 kg | same | same |
In the extended DC input range, the module runs at reduced performance, without overload support and with increased AC output distortion, and the 230 VAC output is limited to 970 W at the low end. The DC port of the 0 W variants remains bidirectional and may carry voltage while mains is present.
Source: Eltek manufacturer product pages (Delta EMEA; 48 V, 110 V and 220 V), November 2026. Specifications are subject to change by the manufacturer.
How to choose
Battery voltage
The model follows from the voltage of the existing or planned battery bank: the manufacturer lists telecom, utility and railway applications for the 48 V modules, and utility, railway and industrial DC systems for the 110 V and 220 V modules. The DC input ranges are 45–58 V, 102–145 V and 204–290 V respectively.
DC output: 1,200 W, 150 W or 0 W
If the module must charge the battery and supply DC loads, specify the 1,200 W model. The 150 W or 0 W variant is an option when battery charging and the DC loads are handled by separate rectifiers; the DC port of the 0 W variant still remains bidirectional.
Combined AC and DC load
The AC load has priority: at full AC load (230 VAC, 1,500 VA), the DC output of the 1,200 W model is limited to 800 W, so 1,200 W AC and 1,200 W DC are not available at the same time. Size the module count for the combined demand of both loads.
System architecture and redundancy
Modules can be paralleled in power cores to build single-phase, three-phase or redundant systems; the CAN and synchronization buses handle load sharing and frequency synchronization. Three-phase systems are built from single-phase modules.
Environment and surge protection
The operating range is −40 to +75 °C. The manufacturer states derating above +55 °C for the 220 V module (from 1,200 W to 480 W at +75 °C) and gives no derating data for the 48 V and 110 V modules. For the 110 V and 220 V modules, plan external AC-port surge protection to meet the 4 kV surge requirement.
Related services and products
- 48 VDC systems
- 72/110 VDC systems
- 220 VDC systems
- DC power systems
- Design and installation
- Maintenance and service
- Eltek Flatpack2 48V HE rectifier modules
- Eltek Smartpack system controllers
Energom Electronic Kft. is an official distributor of Eltek. Services across the Central and Eastern European region; product delivery across Europe. Energom sizes Rectiverter systems based on the AC and DC load, the battery bank and the required redundancy, then handles installation, commissioning and scheduled maintenance.
FAQ
How much AC and DC power does the Rectiverter deliver at the same time?
The Eltek Rectiverter AC output is 1,200 W (1,500 VA), with 2,000 VA for less than 15 s. The AC load has priority: at full AC load and nominal input, the DC output of the 1,200 W model is limited to 800 W; the 0 W versions have no DC output.
Which battery voltages does the Rectiverter support?
The Eltek Rectiverter 230 VAC range covers 48, 110 and 220 VDC battery systems, each in 1,200 W, 150 W and 0 W DC output variants, for nine models in total.
Can the Rectiverter be paralleled?
Eltek Rectiverter modules can be paralleled in power cores to build single-phase, three-phase or redundant systems, with load sharing and frequency synchronization handled over the CAN and synchronization buses.
What happens to the Rectiverter during a grid outage?
During a grid outage, the Rectiverter keeps supplying the AC loads from the connected battery, operating as an inverter. The manufacturer does not state a transfer time.
How efficient is the Rectiverter?
The Rectiverter 230 VAC range reaches above 96% efficiency in grid mode and above 94% in inverter mode; the 110 V module reaches above 95% in inverter mode.
Request a quote
When requesting a quote, include the AC and DC loads, the battery bank voltage (48, 110 or 220 V), the number of phases, the redundancy target and the required backup time.
We respond within 24 hours on business days.