Key specifications at a glance

  • Output: AC: 1200 W (1500 VA), 200–240 VAC, 2000 VA for less than 15 s; DC: 48, 110 or 220 V, max 1200 W (25 / 11.11 / 5.56 A), max 800 W at full AC load; AC load has priority
  • Efficiency: >96% in grid mode; >94% in inverter mode (110 V module: >95%)
  • Input voltage: AC: 185–275 VAC; DC: 45–58 V (48 V), 102–145 V (110 V), 204–290 V (220 V)
  • Operating temperature: −40 to +75 °C (220 V module: derating above +55 °C)
  • Dimensions, weight: 109 × 41.5 × 327 mm (W × H × D); 1.95 kg; hot-pluggable
  • Parallel capability: scalable in parallel power cores to single-phase, three-phase or redundant systems

Applications

  • Telecommunications: backed-up AC and DC power for LTE/4G networks, distributed antenna systems, broadband infrastructure (48 V).
  • Power utilities: switch tripping, SCADA, switchgear, substations, power-generation control and protection.
  • Railway and metro infrastructure: signaling, communications, control centers, converter stations.
  • Critical industrial power with simultaneous AC and 110 or 220 VDC supply.
  • Emergency lighting (220 V).

Rectiverter models: 48 V rectifier module and inverter in one, plus 110 V and 220 V versions

Rectiverter models: 48 V rectifier module and inverter in one, plus 110 V and 220 V versions
Model (part number) Rated output Key difference
Rectiverter 230/1500 48/1200 (241123.100) 1,500 VA AC + max 1,200 W / 25 A DC, 48 V for 48 V battery systems
Rectiverter 230/1500 48/150 (241123.101) 1,500 VA AC + 150 W / 3.13 A DC, 48 V small DC output, primarily AC supply
Rectiverter 230/1500 48/0 (241123.102) 1,500 VA AC, 48 V no DC output (port remains bidirectional)
Rectiverter 230/1500 110/1200 (241123.130) 1,500 VA AC + max 1,200 W / 11.11 A DC, 110 V for 110 V battery systems; inverter efficiency > 95%
Rectiverter 230/1500 110/150 (241123.131) 1,500 VA AC + 150 W / 1.38 A DC, 110 V small DC output
Rectiverter 230/1500 110/0 (241123.132) 1,500 VA AC, 110 V no DC output
Rectiverter 230/1500 220/1200 (241123.140) 1,500 VA AC + max 1,200 W / 5.56 A DC, 220 V for 220 V battery systems
Rectiverter 230/1500 220/150 (241123.141) 1,500 VA AC + 150 W / 0.69 A DC, 220 V small DC output
Rectiverter 230/1500 220/0 (241123.142) 1,500 VA AC, 220 V no DC output

Technical specifications

Technical specifications
Parameter 48 V modules 110 V modules 220 V modules
AC output 1,200 W (1,500 VA), 200–240 VAC; 2,000 VA for less than 15 s same same
Default inverter frequency 50 Hz, adaptive 50 Hz, adaptive 50 Hz, adaptive
Optional output frequency 94–106 Hz or 74–76 Hz, depending on hardware and firmware revision 94–106 Hz, firmware 1.20/1.20 or later 94–106 Hz, firmware 1.10/1.10 or later
AC output THD < 1.5% with a resistive load < 1.5% with a resistive load < 1.5% with a resistive load
DC output (1,200 W model) max 1,200 W / 25 A max 1,200 W / 11.11 A max 1,200 W / 5.56 A
DC output (150 W model) 150 W / 3.13 A at output voltages of 48 VDC or lower 150 W / 1.38 A at output voltages of 108 VDC or lower 150 W / 0.69 A at output voltages of 216 VDC or lower
DC output at full 230 VAC load (1,200 W model, nominal input) max 800 W (16.6 A) max 800 W (7.4 A) max 800 W
Adjustable DC output voltage 43–58 VDC, default 53.5 VDC 97–145 VDC, default 122.5 VDC 194–290 VDC, default 245 VDC
AC input 185–275 VAC; disconnect at 170 VAC same same
DC input 45–58 V 102–145 V 204–290 V
Extended DC input range 40–45 VDC 90–102 VDC 180–204 VDC
Maximum battery current 32 A, 45 A for 15 s 12.5 A, 18 A for 15 s 6.67 A, 9 A for 15 s
Efficiency, grid mode >96% >96% >96%
Efficiency, inverter mode >94% >95% >94%
Operating temperature −40 to +75 °C; derating not stated −40 to +75 °C; derating not stated −40 to +75 °C; derating above +55 °C, from 1,200 W to 480 W at +75 °C
Relative humidity 5–95% RH, non-condensing 5–95% RH, non-condensing 5–95% RH, non-condensing
MTBF 260,000 hours at +25 °C 260,000 hours at +25 °C not stated
Protection fuses, transient suppression, output overvoltage shutdown, short-circuit protection, DC reverse-polarity protection same, plus OR-ing FET same as the 48 V modules
AC-port surge protection not stated external AC-port surge protection is required to meet the 4 kV surge requirement external AC-port surge protection is required to meet the 4 kV surge requirement
Communication CAN and synchronization buses: adaptive frequency, parallel load sharing, alarms, system-level control same same
Dimensions (W × H × D), weight 109 × 41.5 × 327 mm; 1.95 kg same same

In the extended DC input range, the module runs at reduced performance, without overload support and with increased AC output distortion, and the 230 VAC output is limited to 970 W at the low end. The DC port of the 0 W variants remains bidirectional and may carry voltage while mains is present.

Source: Eltek manufacturer product pages (Delta EMEA; 48 V, 110 V and 220 V), November 2026. Specifications are subject to change by the manufacturer.

How to choose

Battery voltage

The model follows from the voltage of the existing or planned battery bank: the manufacturer lists telecom, utility and railway applications for the 48 V modules, and utility, railway and industrial DC systems for the 110 V and 220 V modules. The DC input ranges are 45–58 V, 102–145 V and 204–290 V respectively.

DC output: 1,200 W, 150 W or 0 W

If the module must charge the battery and supply DC loads, specify the 1,200 W model. The 150 W or 0 W variant is an option when battery charging and the DC loads are handled by separate rectifiers; the DC port of the 0 W variant still remains bidirectional.

Combined AC and DC load

The AC load has priority: at full AC load (230 VAC, 1,500 VA), the DC output of the 1,200 W model is limited to 800 W, so 1,200 W AC and 1,200 W DC are not available at the same time. Size the module count for the combined demand of both loads.

System architecture and redundancy

Modules can be paralleled in power cores to build single-phase, three-phase or redundant systems; the CAN and synchronization buses handle load sharing and frequency synchronization. Three-phase systems are built from single-phase modules.

Environment and surge protection

The operating range is −40 to +75 °C. The manufacturer states derating above +55 °C for the 220 V module (from 1,200 W to 480 W at +75 °C) and gives no derating data for the 48 V and 110 V modules. For the 110 V and 220 V modules, plan external AC-port surge protection to meet the 4 kV surge requirement.

Related services and products

Energom Electronic Kft. is an official distributor of Eltek. Services across the Central and Eastern European region; product delivery across Europe. Energom sizes Rectiverter systems based on the AC and DC load, the battery bank and the required redundancy, then handles installation, commissioning and scheduled maintenance.

FAQ

How much AC and DC power does the Rectiverter deliver at the same time?

The Eltek Rectiverter AC output is 1,200 W (1,500 VA), with 2,000 VA for less than 15 s. The AC load has priority: at full AC load and nominal input, the DC output of the 1,200 W model is limited to 800 W; the 0 W versions have no DC output.

Which battery voltages does the Rectiverter support?

The Eltek Rectiverter 230 VAC range covers 48, 110 and 220 VDC battery systems, each in 1,200 W, 150 W and 0 W DC output variants, for nine models in total.

Can the Rectiverter be paralleled?

Eltek Rectiverter modules can be paralleled in power cores to build single-phase, three-phase or redundant systems, with load sharing and frequency synchronization handled over the CAN and synchronization buses.

What happens to the Rectiverter during a grid outage?

During a grid outage, the Rectiverter keeps supplying the AC loads from the connected battery, operating as an inverter. The manufacturer does not state a transfer time.

How efficient is the Rectiverter?

The Rectiverter 230 VAC range reaches above 96% efficiency in grid mode and above 94% in inverter mode; the 110 V module reaches above 95% in inverter mode.

Request a quote

When requesting a quote, include the AC and DC loads, the battery bank voltage (48, 110 or 220 V), the number of phases, the redundancy target and the required backup time.

Request a Quote

We respond within 24 hours on business days.

Request a Callback