Key specifications at a glance

  • Output power factor: 1.0 (ratings given in kW)
  • Topology: online, double-conversion, modular; VFI-SS-111 (IEC 62040-3)
  • Power module: 67 kW, 3U: MP2 67 PM (IGBT) or MP2 67 PM BLUE (SiC); M2S 2000 and all top-ventilation versions with BLUE modules only
  • Efficiency (online mode): max 96.5% with IGBT module; max 98.1% with BLUE (SiC) module
  • Input THDi: <3%
  • Parallel capability: max 4 units; max 4,000 / 5,000 / 6,400 / 8,000 kW in total (M2S 1000 / 1250 / 1600 / 2000)

Applications

  • Large data centers and other critical facilities
  • AI applications with rapidly fluctuating load profiles
  • Critical loads in industrial and transport facilities

Multi Power2 Scalable (M2S) modular UPS models

Multi Power2 Scalable (M2S) modular UPS models
Model Rated power Key feature
M2S 1000 (PC0, PCS, CT0, CT2) 1,000 kW 16 module slots, 15 modules for full power
M2S 1250 (PC0, PCS, CT0, CT2) 1,250 kW 20 module slots, 19 modules for full power
M2S 1600 (PC0, PCS, CT0, CT2) 1,600 kW 30 module slots, 24 modules for full power
M2S 2000 PC0 F VE 2,000 kW 30 × MP2 67 PM BLUE modules, without switches, flange connection, top ventilation

Versions: PC0 – without switches; PCS – full switch set; CT0 – embedded backfeed protection device, without switches; CT2 – embedded backfeed protection device with input and output switches. Ratings below the unit's nominal power are set by the number of installed modules.

Technical specifications

Technical specifications
Parameter Value
Unit nominal and bypass power M2S 1000: 1,000 kW; M2S 1250: 1,250 kW; M2S 1600: 1,600 kW; M2S 2000: 2,000 kW (bypass power identical)
Module slots and modules for full power M2S 1000: 16 slots, 15 modules; M2S 1250: 20 slots, 19 modules; M2S 1600: 30 slots, 24 modules (MP2 67 PM or PM BLUE); M2S 2000: 30 slots, 30 × MP2 67 PM BLUE
Input rated voltage 380 / 400 / 415 V, three-phase + neutral
Input voltage tolerance 240–480 V (conditions apply)
Input frequency 50 / 60 Hz; tolerance 40–72 Hz
Input power factor 0.99
Input configuration CT0, CT2 and M2S 2000 PC0 F VE: single input only
Bypass voltage tolerance 180 V (adjustable 180–200 V) to 264 V (adjustable 250–264 V), referred to neutral
Bypass frequency tolerance ±5% (adjustable), at 50 or 60 Hz rated frequency
Bypass overload 125% for 10 min; 150% for 1 min
Output rated voltage and frequency 380 / 400 / 415 V, three-phase + neutral (conditions apply for wider tolerance); 50 or 60 Hz
Output voltage stability ±1%
Dynamic stability EN 62040-3 performance class 1, non-linear load
Battery and energy storage types external; VRLA, Li-ion, supercapacitors
Battery arrangement (parallel systems) separate or common battery
Recharging method one-level, two-level or cyclic recharge (selectable)
Operating modes and features (standard) EFFICIENCY CONTROL mode, ACTIVE ECO mode, power walk-in, backfeed detection and protection (CT0 and CT2: embedded protection device), air filter, smart grid ready
Communication (standard) 10-inch color touch screen, LED bar, NetMan 208C network card, configurable I/O signals (10 inputs, 8 outputs), 2 free communication slots, R.E.P.O.
Dimensions (W × D × H) and weight – PC0 M2S 1000: 2,400 × 1,025 × 2,000 mm, 1,949 kg; M2S 1250: 2,400 × 1,025 × 2,000 mm, 2,147 kg; M2S 1600: 3,000 × 1,025 × 2,000 mm, 2,634 kg; M2S 2000 PC0 F VE: 3,600 × 1,025 × 2,250 mm, 3,164 kg
Dimensions (W × D × H) and weight – PCS M2S 1000: 3,000 × 1,025 × 2,000 mm, 2,027 kg; M2S 1250: 3,000 × 1,025 × 2,000 mm, 2,525 kg; M2S 1600: 3,600 × 1,025 × 2,000 mm, 3,012 kg
Dimensions (W × D × H) and weight – CT0 M2S 1000: 2,400 × 1,025 × 2,000 mm, 1,949 kg; M2S 1250: 2,400 × 1,025 × 2,000 mm, 2,147 kg; M2S 1600: 3,000 × 1,025 × 2,000 mm, 2,634 kg
Dimensions (W × D × H) and weight – CT2 M2S 1000: 3,000 × 1,025 × 2,000 mm, 2,055 kg; M2S 1250: 3,000 × 1,025 × 2,000 mm, 2,200 kg; M2S 1600: 3,600 × 1,025 × 2,000 mm, 2,687 kg
Height with top ventilation 2,250 mm (factory option, BLUE modules only; standard on M2S 2000)
Ventilation and cable entry ventilation front to rear (top optional), M2S 2000: front to top; cable entry with front access, top or bottom (CT0: top); M2S 2000 PC0 F VE: top with AC flanges
Noise level <75 dBA ±2 (conditions apply)
Cabinet protection rating IP20 (others on request)
Ambient temperature 0–40 °C
Relative humidity 5–95%, non-condensing
Color RAL 9005
Directives and standards LV 2014/35/EU, EMC 2014/30/EU; safety: IEC EN 62040-1; EMC: IEC EN 62040-2; RoHS compliant

Source: Riello UPS Multi Power2 Scalable 1000–1250–1600–2000 kW catalog sheet (DATM2SM3T26MREN, 2026-11-06). Specifications are subject to change by the manufacturer.

How to choose

Power class and module count

Choose the unit (M2S 1000, 1250, 1600 or 2000) for the final power requirement; intermediate ratings are set by the number of installed 67 kW modules. The M2S 1600 needs 24 of its 30 module slots populated for full power.

Module type: IGBT or BLUE (SiC)

With the MP2 67 PM (IGBT) module, online-mode efficiency is up to 96.5%; with the MP2 67 PM BLUE (SiC) module, up to 98.1%. The M2S 2000 and the top ventilation option work with BLUE modules only.

Version: switches and backfeed protection

The PC0 comes without switches, the PCS with a full switch set. The CT0 and CT2 include an embedded backfeed protection device, and the CT2 adds input and output switches. The CT0, CT2 and M2S 2000 PC0 F VE are single-input only.

Parallel expansion

Up to 4 units can be paralleled; maximum combined power is 4,000 kW with M2S 1000, 5,000 kW with M2S 1250, 6,400 kW with M2S 1600 and 8,000 kW with M2S 2000.

Installation space and batteries

The cabinet lineup is 2,400–3,600 mm wide and 1,025 mm deep, 2,000 mm high or 2,250 mm with top ventilation. All models use external batteries: VRLA, Li-ion or supercapacitors, as separate or common battery banks in parallel systems.

Related services and products

Energom Electronic Kft. is an official distributor of Riello UPS. Energom handles sizing, installation, commissioning and maintenance of Multi Power2 Scalable systems, including selection of the external battery bank. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

Can the Riello UPS Multi Power2 Scalable (M2S) be paralleled?

Yes. Up to 4 Riello UPS Multi Power2 Scalable (M2S) units can operate in parallel; maximum combined power is 4,000 kW with M2S 1000, 5,000 kW with M2S 1250, 6,400 kW with M2S 1600 and 8,000 kW with M2S 2000.

Which power module does the Multi Power2 Scalable (M2S) use?

The Multi Power2 Scalable (M2S) uses the hot-swappable 67 kW, 3U MP2 67 PM (IGBT) or MP2 67 PM BLUE (SiC) module. The M2S 2000 is built with BLUE modules only (30 × MP2 67 PM BLUE), and the factory top-ventilation option on the smaller models also requires BLUE modules.

What is the difference between the M2S PC0, PCS, CT0 and CT2 versions?

The M2S PC0 has no switches and the M2S PCS has a full switch set. The CT0 adds an embedded backfeed protection device without switches, and the CT2 combines backfeed protection with input and output switches; the CT0 and CT2 are single-input only.

What batteries does the Multi Power2 Scalable (M2S) use?

The M2S uses external batteries; the manufacturer lists VRLA, Li-ion and supercapacitor energy storage. Parallel systems can use separate or common batteries.

Request a quote

For an accurate quote, include the protected load and planned expansion in kW, the nature of the load profile, the required redundancy, the backup time, the preferred version (switches, backfeed protection) and the dimensions of the installation space.

Request a Quote

We respond within 24 hours on business days.

Request a Callback