Key specifications at a glance

  • Output power factor: 1.0 (ratings given in kW)
  • Topology: online, double-conversion, modular; VFI-SS-111 (IEC 62040-3)
  • Power module: 15 kW (M2X 15 PM, M2X 15 PM BLUE) or 30 kW (M2X 30 PM BLUE), 2U
  • Efficiency (online mode): max 98%
  • Input THDi: <3%
  • Parallel capability: max 6 units; max 480 kW in total (M2X 120 cabinets) or 360 kW (M2X 90 CBC 4)

Applications

  • Protection of IT environments in small data centers and server rooms
  • Critical applications where the load must keep running through grid disturbances
  • Digital systems in healthcare, telecommunications, commerce and education
  • Critical loads in transport infrastructure

Multi Power2-M2X modular UPS models

Multi Power2-M2X modular UPS models
Model Rated power Key feature
M2X 120 PCS 75 kW (15 kW modules) / 120 kW (30 kW modules) power cabinet with 5 module slots, no batteries; front-access bottom cable entry
M2X 120 CBC 6 75 kW (15 kW modules) / 120 kW (30 kW modules) Combo cabinet with 5 module slots and 6 battery shelves
M2X 90 CBC 4 45 kW (15 kW modules) / 90 kW (30 kW modules) Combo cabinet with 3 module slots and 4 battery shelves

The cabinets accept the M2X 15 PM and M2X 15 PM BLUE (15 kW) and the M2X 30 PM BLUE (30 kW) power modules. A cabinet rating of 120 kW requires the 30 kW modules.

Technical specifications

Technical specifications
Parameter Value
Input rated voltage 380 / 400 / 415 V, three-phase + neutral
Input voltage tolerance 240–480 V (conditions apply)
Input frequency 50 / 60 Hz; tolerance 40–72 Hz
Input power factor 0.99
Bypass nominal power 90–120 kW, according to system power configuration
Bypass voltage tolerance 180 V (adjustable 180–200 V) to 264 V (adjustable 250–264 V), referred to neutral
Bypass frequency tolerance ±5% (adjustable), at 50 or 60 Hz rated frequency
Bypass overload 125% for 10 min; 150% for 1 min
Output rated voltage and frequency 380 / 400 / 415 V, three-phase + neutral (conditions apply for wider tolerance); 50 or 60 Hz
Output voltage stability ±1%
Dynamic stability EN 62040-3 performance class 1, non-linear load
Battery and energy storage types VRLA, Li-ion, supercapacitors
Battery arrangement (parallel systems) separate or common battery
Recharging method one-level, two-level or cyclic recharge (selectable)
Module slots and layout M2X 120 PCS and M2X 120 CBC 6: 5 module slots (4+1 × M2X 30 PM BLUE or 5 × M2X 15 PM / M2X 15 PM BLUE); M2X 90 CBC 4: 3 module slots (3 × M2X 30 PM BLUE, M2X 15 PM or M2X 15 PM BLUE)
Battery shelves M2X 120 CBC 6: 6 shelves (max 6 strings); M2X 90 CBC 4: 4 shelves (max 4 strings); M2X 120 PCS: none
Operating modes and features (standard) EFFICIENCY CONTROL mode (adjusts the number of active power modules to the load), fan monitoring, backfeed detection and protection, power walk-in
Communication (standard) 10-inch color touch screen, LED bar, NetMan 208 network card, configurable I/O signals (5 inputs, 4 outputs), 2 free communication slots, R.E.P.O. (remote emergency power off)
Cabinet protection rating IP20 (others on request)
Ambient temperature 0–40 °C; no derating up to 40 °C
Relative humidity 5–95%, non-condensing
Noise level 60 dBA ±2 (conditions apply)
Ventilation front to rear (M2X 120 CBC 6: front-to-top optional)
Cable entry M2X 120 PCS: front access, bottom; Combo cabinets: rear, top or bottom
Dimensions (W × D × H) M2X 120 PCS: 600 × 940 × 1,590 mm; M2X 120 CBC 6: 600 × 985 × 1,995 mm; M2X 90 CBC 4: 600 × 985 × 1,590 mm
Weight M2X 120 PCS: 301 kg (with 5 modules); M2X 120 CBC 6: 1,148 kg (with 5 modules and 6 fully populated battery shelves); M2X 90 CBC 4: 790 kg (with 3 modules and 4 fully populated shelves)
Color RAL 9005
Directives and standards LV 2014/35/EU, EMC 2014/30/EU; safety: IEC EN 62040-1; EMC: IEC EN 62040-2; RoHS compliant

Source: Riello UPS Multi Power2-M2X catalog sheet (DATM2XM3P26AREN, 2026-01-20) and Riello UPS product page (November 2026). Specifications are subject to change by the manufacturer.

How to choose

Load and module size

With 15 kW modules (M2X 15 PM, M2X 15 PM BLUE), the M2X 120 cabinets scale up to 75 kW and the M2X 90 CBC 4 up to 45 kW. Larger loads (above 75 kW in an M2X 120 cabinet, above 45 kW in the M2X 90 CBC 4) call for the 30 kW M2X 30 PM BLUE module, which takes the M2X 120 cabinets up to 120 kW and the M2X 90 CBC 4 up to 90 kW.

Redundancy within the cabinet

With 4+1 × 30 kW modules in the five slots of the M2X 120 PCS or M2X 120 CBC 6, the 120 kW rating is available with N+1 redundancy. Modules are hot-swappable, and capacity can be added while the system is running.

Where the batteries go

If the room has no space for a separate battery cabinet, a Combo cabinet holds the batteries internally (M2X 120 CBC 6: up to 6 strings; M2X 90 CBC 4: up to 4 strings). The M2X 120 PCS power cabinet runs on external batteries. Supported technologies: VRLA, Li-ion or supercapacitors.

Scaling through parallel operation

Up to 6 units can be paralleled for up to 480 kW in total (M2X 120 cabinets) or 360 kW (M2X 90 CBC 4), with separate or common batteries.

Installation space

All cabinets are 600 mm wide. The M2X 120 PCS has front access and bottom cable entry; the Combo cabinets take cables at the rear, from the top or bottom. Operating temperature is 0–40 °C, and the protection rating is IP20.

Related services and products

Energom Electronic Kft. is an official distributor of Riello UPS. Energom handles sizing, installation, commissioning and maintenance of Multi Power2-M2X systems, including battery selection. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

Can the Riello UPS Multi Power2-M2X be paralleled?

Yes. Up to 6 Riello UPS Multi Power2-M2X units can operate in parallel, for up to 480 kW in total (M2X 120 cabinets) or 360 kW (M2X 90 CBC 4), with separate or common batteries.

What batteries does the Multi Power2-M2X support?

According to the manufacturer's datasheet, the Multi Power2-M2X works with VRLA, Li-ion or supercapacitor energy storage. The Combo cabinets have internal battery shelves (M2X 120 CBC 6: 6 shelves; M2X 90 CBC 4: 4 shelves), while the M2X 120 PCS uses external batteries.

Can Multi Power2-M2X capacity be expanded while the system is running?

Yes. The Multi Power2-M2X 2U power modules are hot-swappable and can be added during operation; an M2X 120 cabinet scales up to 120 kW with 30 kW modules or 75 kW with 15 kW modules (M2X 90 CBC 4: 90 or 45 kW).

What is the efficiency of the Multi Power2-M2X?

The Multi Power2-M2X reaches up to 98% efficiency in online (double-conversion) mode. The manufacturer's datasheet does not state an ECO mode efficiency.

Request a quote

For an accurate quote, include the protected load in kW, the required redundancy (for example N+1), the backup time, where the batteries should go (inside a Combo cabinet or separately) and the cable entry options at the installation site.