Key specifications at a glance

  • Output power factor: 1.0 (kW = kVA), up to 40 °C
  • Topology: online, double-conversion, transformer-free; VFI-SS-111 (IEC 62040-3)
  • Efficiency (online mode): max 97%
  • Efficiency (ACTIVE ECO / ECO mode): 98.5% (ACTIVE ECO); 99% (ECO)
  • Input THDi: <3%
  • Parallel capability: max 8 units, capacity or N+1 redundant; common or separate battery

Applications

  • Data centers and communication networks
  • Critical loads in commercial and industrial facilities
  • Sites with limited supply capacity (for example a diesel generator or a contractually limited grid connection), where peak shaving covers the excess demand from the batteries
  • Data center distribution without a neutral conductor, and replacement of legacy equipment
  • Medical, emergency-system, industrial and transport applications

NextEnergy (NXE) online UPS models

NextEnergy (NXE) online UPS models
Model Rated power Key feature
NXE 250 250 kVA / 250 kW 800 mm wide cabinet, bottom cable entry
NXE 300 300 kVA / 300 kW 1,200 mm wide, top and bottom cable entry
NXE 400 400 kVA / 400 kW 1,400 mm wide, top and bottom cable entry
NXE 500 500 kVA / 500 kW 1,600 mm wide, bottom cable entry
NXE 600 600 kVA / 600 kW 2,000 mm wide, bottom cable entry
NXE 800 2SW 800 kVA / 800 kW 2,000 mm wide version (NXE 800: 2,400 mm), bottom cable entry
NXE 800 800 kVA / 800 kW 2,400 mm wide, top and bottom cable entry

Technical specifications

Technical specifications
Parameter Value
Input rated voltage 380 / 400 / 415 V, three-phase
Input voltage tolerance 400 V ±20% at full load (conditions apply for wider tolerance)
Input frequency tolerance 40–70 Hz
Input power factor 0.99
Soft start 0–100% in 120 s (selectable)
Standard equipment backfeed protection, separate bypass line
Output voltage and frequency 380 / 400 / 415 V, three-phase + N (selectable); 50 or 60 Hz (selectable)
Output voltage stability ±1% static; ±5% in 10 ms dynamic
Output voltage distortion <1% with linear load; <3% with non-linear load
Frequency stability on battery ±0.05%
Overload (inverter) NXE 250 and NXE 500: 110% for 60 min, 125% for 2 min, 150% for 20 s; NXE 300, NXE 400, NXE 600, NXE 800 2SW and NXE 800: 110% for 60 min, 125% for 10 min, 150% for 1 min
Bypass frequency tolerance ±2% (selectable from ±1% to ±5%); 50 or 60 Hz
Transfer time from ECO mode to ONLINE mode on mains failure approx. 2 ms; approx. 0 in ACTIVE ECO mode (VFD-SS-111)
Peak shaving settable max input power (kW or kVA); static, user remote control and dynamic modes
Three-wire or four-wire operation operates with (4-wire) or without (3-wire) neutral connection
Parallel system features Efficiency Control Mode (ECM): at low load some units are set to “freeze” mode; Hot System Expansion (HSE): expansion without switching off or transferring the operating units to bypass
Battery and energy storage types external; VRLA AGM and GEL, NiCd, supercapacitors, Li-ion
Battery charging ripple current: zero; temperature-compensated recharge voltage
Communication and control USB, dry contacts, 2 slots for communication interfaces, Ethernet port; remote controls: EPO, bypass, battery charge block (configurable); 7-inch color touch screen (800 × 480 pixels), 3 password levels
Protocols embedded: PowerShield3 and email over Ethernet; with NetMan 208 card: Modbus/TCP and SNMP
Dimensions (W × D × H) NXE 250: 800 × 850 × 1,900 mm; NXE 300: 1,200 × 850 × 1,900 mm; NXE 400: 1,400 × 850 × 1,900 mm; NXE 500: 1,600 × 850 × 1,900 mm; NXE 600 and NXE 800 2SW: 2,000 × 850 × 1,900 mm; NXE 800: 2,400 × 850 × 1,900 mm
Weight NXE 250: 634 kg; NXE 300: 880 kg; NXE 400: 1,100 kg; NXE 500: 1,300 kg; NXE 600: 1,600 kg; NXE 800 2SW: 1,800 kg; NXE 800: 1,985 kg
Cable entry NXE 250, 500, 600 and 800 2SW: bottom; NXE 300, 400 and 800: top and bottom
Noise level (at 1 m, 50% and 100% load) NXE 250, 300 and 400: 63 dBA and 70 dBA; NXE 500: 65 dBA and 73 dBA; NXE 600: 66 dBA and 73 dBA; NXE 800: 68 dBA and 74 dBA
Protection rating IP20 (others on request; IP21 and IP31 versions optional)
Ambient temperature 0–40 °C (recommended for battery life: 20–25 °C); relative humidity 5–95%, non-condensing
Color RAL 7016
Directives and standards LV 2014/35/EU, EMC 2014/30/EU; safety: IEC EN 62040-1; EMC: IEC EN 62040-2; RoHS compliant

Source: Riello UPS NextEnergy 250–800 kVA catalog sheet (DATNXEG3Y23BREN, 2025-08-04), supplemented by the per-model technical data on the Riello UPS product page (November 2026). Specifications are subject to change by the manufacturer.

How to choose

Power rating and cabinet size

Cabinet widths across the six power ratings (250, 300, 400, 500, 600 and 800 kVA) range from 800 to 2,400 mm. At 800 kVA there are two versions: the NXE 800 2SW is 2,000 mm wide, the NXE 800 is 2,400 mm wide.

Limited supply and peak shaving

Where supply capacity is limited (for example a diesel generator or a contractually limited grid connection), the maximum input power can be set in kW or kVA, and the UPS supplies the portion of the load above that limit from its batteries. Static, user remote control and dynamic modes are available.

Operating mode and efficiency

Efficiency is up to 97% in online double-conversion mode, 98.5% in ACTIVE ECO mode (VFD-SS-111, with a transfer time of approx. 0) and 99% in ECO mode (approx. 2 ms transfer to ONLINE mode on mains failure).

Redundancy and expansion

Up to 8 units can be paralleled for capacity or N+1 redundancy, with common or separate batteries. Hot System Expansion (HSE) allows the system to grow without shutting down the operating units.

Distribution system and batteries

The NXE operates with a neutral (4-wire) or without one (3-wire), which matters for legacy equipment replacement and for distribution without a neutral. Battery options: VRLA AGM or GEL, NiCd, Li-ion or supercapacitors.

Related services and products

Energom Electronic Kft. is an official distributor of Riello UPS. Energom handles sizing, installation, commissioning and maintenance of NextEnergy systems, including selection of the external battery bank. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

Can the Riello UPS NextEnergy (NXE) be paralleled?

Yes. Up to 8 Riello UPS NextEnergy (NXE) units can operate in parallel for capacity or N+1 redundancy, with common or separate batteries. With Hot System Expansion (HSE), the system can be expanded without switching off the operating units or transferring them to bypass.

How does NextEnergy peak shaving work?

On the NextEnergy (NXE), the upper limit of input power is set in kW or kVA, and the UPS supplies the portion of the load above that limit from its batteries. Static, user remote control and dynamic modes are available, for example for sites supplied by a diesel generator or a contractually limited grid connection.

What batteries does the NextEnergy (NXE) support?

The NXE uses external batteries; the manufacturer lists VRLA AGM and GEL, NiCd, Li-ion and supercapacitor energy storage. The recommended battery operating temperature is 20–25 °C.

Can the NextEnergy (NXE) run without a neutral conductor?

Yes. The NXE operates with a neutral (four-wire) or without one (three-wire), so it suits data center distribution without a neutral and the replacement of legacy equipment.