Key specifications at a glance

  • Output power factor: 1.0 (kW = kVA), up to 40 °C
  • Topology: online, double-conversion, transformer-free; VFI-SS-111 (IEC EN 62040-3)
  • Efficiency (online mode): max 96.6% (series-level value)
  • Efficiency (ECO / SMART ACTIVE mode): max 99%
  • Input THDi: ≤3%
  • Parallel capability: max 8 units, N+1 redundant or capacity (three-phase-output S3T models)

Applications

  • Small data centers and mission-critical applications
  • Blade servers and capacitive loads
  • Installations with limited mains power or generator supply
  • Loads generating harmonic currents
  • Central power supply systems (CPSS) for emergency lighting
  • Electro-medical, emergency, industrial and transport applications

Sentryum models

Sentryum models
Model Rated power Distinguishing feature
S3M 10 / 15 / 20 (CPT, ACT, XTD) 10 / 15 / 20 kVA/kW single-phase output, three- or single-phase input
S3T 10 / 15 / 20 CPT (Compact) 10 / 15 / 20 kVA/kW smallest cabinet (280 × 840 × 700 mm), space for 40 internal battery blocks
S3T 10–60 ACT (Active) 10 / 15 / 20 / 30 / 40 / 60 kVA/kW space for 2 × 40 internal battery blocks (no internal battery at 60 kVA/kW)
S3T 10–60 XTD (Xtend) 10 / 15 / 20 / 30 / 40 / 60 kVA/kW space for 3 × 40 internal battery blocks, optional internal isolation transformer, IP21 and IP31 option
S3T 80 / 100 / 120 80 / 100 / 120 kVA/kW dedicated cabinet, no internal battery, IP21 and IP31 option

UPS technical specifications

UPS technical specifications
Parameter Value
Input rated voltage 380 / 400 / 415 V three-phase + N; S3M also 220 / 230 / 240 V single-phase + N
Input voltage tolerance 400 V ±20% (S3M: 230 V and 400 V ±20%) at full load; up to −40% at half load
Input frequency range 40–72 Hz
Input power factor 0.99 at full load
Bypass voltage tolerance from 180 V (adjustable 180–200 V) to 264 V (adjustable 250–264 V), phase-to-neutral; frequency tolerance ±5% (selectable)
Bypass overload 110% continuous; 125%: 60 min; 150%: 10 min
Inverter overcurrent max 270% for 200 ms; 150% for 300 ms
Output voltage 380 / 400 / 415 V three-phase + N (S3T); 220 / 230 / 240 V single-phase + N (S3M); selectable
Output current (inverter / bypass) 43 / 48 A (S3M 10); 65 / 72 A (S3M 15); 87 / 96 A (S3M 20); 14.5 / 16 A (S3T 10); 21.7 / 24 A (S3T 15); 29 / 32 A (S3T 20); 43.5 / 48 A (S3T 30); 58 / 64 A (S3T 40); 86.6 / 95 A (S3T 60); 116 / 128 A (S3T 80); 145 / 160 A (S3T 100); 174 / 192 A (S3T 120)
Output voltage distortion <1% with resistive linear load; ≤1.5% with non-linear load
Output stability voltage: ±1%; frequency on battery: 0.01%; dynamic: IEC EN 62040-3 class 1, non-linear load
Inverter three-level NPC; switching frequency 18 kHz (10–60 kVA/kW), 16 kHz (80–120 kVA/kW)
Operating modes ON LINE, ECO, SMART ACTIVE, STANDBY OFF; frequency-converter mode; cold start from battery
Efficiency online double-conversion mode: max 96.6% (series-level value); SMART ACTIVE mode: max 99%; ECO mode: max 99% (per the manufacturer's product page)
Battery and energy storage types VRLA AGM and GEL, open vented, NiCd, lithium-ion, supercapacitors
Battery blocks per string standard 20 + 20 × 12 V blocks with central neutral point; adjustable from 15 + 15 to 22 + 22 (automatic power derating below 20 + 20)
Internal battery space CPT: 40 blocks; ACT: 2 × 40 blocks (S3T ACT 60: none); XTD: 3 × 40 blocks (S3T XTD 60: 3 × 40 × 9 Ah); S3T 80–120: none
Charging methods one-level, two-level (IU), cyclic (selectable); temperature-compensated charging voltage
Charging current max 30 A (S3T 40–120)
Dual input Compact: no; Active and S3T 80–120: optional; Xtend: standard
Isolation transformer Xtend: internal option; Compact, Active, S3T 80–120: external
Communications color graphic touch screen, status LED bar; USB, RS232 (RJ10); 2 communication slots; contact interface with 5 opto-isolated inputs and 4 relay outputs; R.E.P.O.
Dimensions (W × D × H) Compact: 280 × 840 × 700 mm; Active: 380 × 850 × 1,025 mm; Xtend: 440 × 840 × 1,320 mm; S3T 80–120: 500 × 830 × 1,600 mm
Weight (without batteries) CPT / ACT / XTD: 48 / 72 / 103 kg (10 kVA/kW); 50 / 74 / 105 kg (15 kVA/kW); 52 / 76 / 107 kg (20 kVA/kW); ACT / XTD: 78 / 112 kg (S3T 30); 82 / 116 kg (S3T 40); 87 / 130 kg (S3T 60); 172 / 180 / 198 kg (S3T 80 / 100 / 120)
Degree of protection IP20; IP21 and IP31 as option (XTD and S3T 80–120)
Operating temperature 0–40 °C (recommended for battery life: 20–25 °C)
Relative humidity 5–95%, non-condensing
Noise level (at 1 m, SMART ACTIVE mode, ±2 dBA) <40 dBA (S3M 10–20, S3T 10–40); <50 dBA (S3T 60); <55 dBA (S3T 80–120)
Standards and directives VFI-SS-111 (IEC EN 62040-3); safety: IEC EN 62040-1; EMC: IEC EN 62040-2; 2014/35/EU (LVD), 2014/30/EU (EMC); RoHS compliant

Source: Riello UPS catalog sheet (DATS3TD2T23BREN, June 2023) and Riello UPS product page model tables (November 2026). Specifications are subject to change by the manufacturer.

How to choose

Output phases and power

For single-phase output, the S3M 10, 15 and 20 kVA/kW models fit, and they run from either a three-phase or a single-phase input. For three-phase output, S3T models cover 10 to 120 kVA/kW.

Cabinet size and internal battery space

The Compact (CPT) cabinet gives the smallest footprint up to 20 kVA/kW, with space for 40 internal battery blocks. Active (ACT) holds 2 × 40 blocks and Xtend (XTD) 3 × 40 blocks for longer internal runtime. The S3T ACT 60 and S3T 80–120 require an external battery bank.

Battery technology

The Sentryum works with VRLA AGM and GEL, open vented, NiCd and lithium-ion batteries, as well as supercapacitors. The standard string is 20 + 20 × 12 V blocks; block count is adjustable from 15 + 15 to 22 + 22, with automatic power derating below 20 + 20 blocks.

Redundancy and expansion

Three-phase-output S3T models can run up to 8 units in parallel for N+1 redundancy or added capacity. The manufacturer gives no parallel unit count for the single-phase-output S3M models, so such configurations need case-by-case confirmation.

Input supply, isolation and site conditions

For a separate bypass feed, dual input is standard on Xtend and optional on Active and S3T 80–120. For galvanic isolation, Xtend takes an internal isolation transformer; the other versions can use an external isolation transformer. Protection above IP20 (IP21 and IP31) is available on Xtend and S3T 80–120.

Related services and products

Energom Electronic Kft. is an official distributor of Riello UPS. Energom sizes Sentryum systems and designs the battery bank to the load, the redundancy requirement and the required runtime, then handles installation, commissioning and scheduled maintenance. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

Can the Riello UPS Sentryum be paralleled?

Riello UPS Sentryum S3T models with three-phase output can run up to 8 units in parallel, for N+1 redundancy or added capacity. The manufacturer does not state a parallel unit count for the single-phase-output S3M models.

What batteries does the Sentryum support?

The Sentryum works with VRLA AGM and GEL, open vented, NiCd and lithium-ion batteries, as well as supercapacitors. The standard string is 20 + 20 × 12 V blocks with a central neutral point; the block count is adjustable from 15 + 15 to 22 + 22, with automatic power derating below 20 + 20 blocks.

Does the Sentryum have internal batteries?

Sentryum internal battery space depends on the cabinet: Compact holds 40 blocks, Active 2 × 40 and Xtend 3 × 40 internal battery blocks. The S3T ACT 60 and the S3T 80, 100 and 120 have no internal battery space and need an external battery bank.

Can the Sentryum run on generator power?

The manufacturer recommends the Sentryum for installations with limited mains power or generator supply. Input THDi of ≤3%, an input power factor of 0.99 at full load and a 40–72 Hz input frequency range are the starting data for sizing the generator.

Is the Riello UPS Sentryum three-phase or single-phase?

The Riello UPS Sentryum comes in both versions. S3T models have three-phase input and output from 10 to 120 kVA/kW; S3M models deliver single-phase output from a three-phase or single-phase input, from 10 to 20 kVA/kW.

Request a quote

For a quote, share the protected load (kVA and kW), the number of output phases, the required runtime and battery technology, the redundancy requirement and the available space.

Request a Quote

We respond within 24 hours on business days.

Request a Callback