Key specifications at a glance

  • Output power factor: 1.0 (kW = kVA), up to 40 °C
  • Topology: online, double-conversion; VFI-SS-111 (IEC EN 62040-3)
  • Efficiency (online mode): max 96.3%
  • Efficiency (SMART ACTIVE mode): max 99%
  • Input THDi: ≤3%
  • Parallel capability: max 8 modules, 160 kVA/kW in total; max 3 modules per cabinet (60 kVA/kW), with a parallel kit per module

Applications

  • Industrial processes and industrial environments with a disturbed supply grid
  • Electro-medical applications
  • Emergency systems
  • Transport

Sentryum Rack models

Sentryum Rack models
Model Rated power Distinguishing feature
SRM 20 20 kVA/kW (module) single-phase output, standalone module for a 19-inch enclosure (9U, 664 mm deep, 41 kg)
SRT 20 20 kVA/kW (module) three-phase output, standalone module for a 19-inch enclosure (9U, 664 mm deep, 41 kg)
SRM 60 PWC max 60 kVA/kW per cabinet (3 modules) single-phase-output Sentryum Rack cabinet with distribution panel and manual maintenance bypass
SRT 60 PWC max 60 kVA/kW per cabinet (3 modules) three-phase-output Sentryum Rack cabinet with distribution panel and manual maintenance bypass

Modular UPS technical specifications

Modular UPS technical specifications
Parameter Value
Module rating 20 kVA / 20 kW
Input rated voltage 220 / 230 / 240 V single-phase + N and 380 / 400 / 415 V three-phase + N; input arrangement detected automatically
Input voltage tolerance 230 V and 400 V ±20% at full load; up to −40% at half load
Input frequency range 40–72 Hz
Input power factor 0.99 at full load
Bypass voltage tolerance from 180 V (adjustable 180–200 V) to 264 V (adjustable 250–264 V), phase-to-neutral; frequency tolerance ±5% (selectable); separate bypass input
Bypass overload 110% continuous; 125%: 60 min; 150%: 10 min
Inverter three-level IGBT
Inverter overcurrent max 270% for 200 ms; 150% for 300 ms
Operating modes SMART ACTIVE; cold start from battery
Output voltage 220 / 230 / 240 V single-phase + N (SRM); 380 / 400 / 415 V three-phase + N (SRT); selectable
Output voltage distortion <1% with resistive linear load; ≤1.5% with non-linear load
Output stability voltage: ±1%; frequency on battery: 0.01%; dynamic: IEC EN 62040-3 class 1, non-linear load
Battery and energy storage types external only: VRLA AGM and GEL, open vented, NiCd, lithium-ion, supercapacitors
Battery blocks per string standard 20 + 20 × 12 V blocks with central neutral point; adjustable from 15 + 15 to 22 + 22
Charging methods one-level, two-level (IU), cyclic (selectable); temperature-compensated charging voltage
Charging current max 20 A per module
Power module dimensions and weight 445 × 664 × 397 mm (19-inch wide, 9U); 41 kg
Cabinet dimensions and weight (SRM 60 PWC, SRT 60 PWC) 700 × 750 × 2,060 mm; 165 kg without power modules; max 3 modules per cabinet
Cabinet equipment (SRM 60 PWC, SRT 60 PWC) per module: rectifier-input, bypass-input and output disconnectors, battery fuse holder; manual maintenance bypass for all 3 modules
Connections front-accessible Harting plug-in power connectors (inputs, output, battery); standalone module supplied with 3 m loose cables
Communications (per module) 5-inch graphic touch screen (can be remoted up to 2 m), status LED bar; USB, RS232 (RJ10); 2 communication slots; contact interface with 5 opto-isolated inputs and 4 relay outputs; R.E.P.O.
Degree of protection IP20
Operating temperature 0–40 °C (recommended for battery life: 20–25 °C)
Relative humidity 5–95%, non-condensing
Noise level <40 dBA for a single power module, at 1 m, SMART ACTIVE mode, ±2 dBA
Standards and directives VFI-SS-111 (IEC EN 62040-3); safety: IEC EN 62040-1; EMC: IEC EN 62040-2; 2014/35/EU (LVD), 2014/30/EU (EMC); RoHS compliant
Color RAL 9005

Source: Riello UPS catalog sheet (DATSRTD2T23BREN, March 2023) and Riello UPS product page model tables (November 2026). Specifications are subject to change by the manufacturer.

How to choose

Output phases

SRM models deliver single-phase output (220 / 230 / 240 V) and SRT models three-phase output (380 / 400 / 415 V). Both run from a single-phase or three-phase input; the module detects the input arrangement automatically.

Power and expansion

The building block is the 20 kVA/kW module. A Sentryum Rack cabinet holds up to 3 modules (60 kVA/kW) on the same footprint; with a parallel kit per module, up to 8 modules and 160 kVA/kW can be combined. Modules are replaced or added from the front.

Standalone module or Sentryum Rack cabinet

The SRM 20 and SRT 20 standalone modules mount in a 19-inch cabinet or mounting frame and ship with 3 m loose cables on their Harting connectors. Each module measures 445 × 664 × 397 mm (9U) and weighs 41 kg, so check the cabinet's usable mounting depth and the rail load rating in advance. The SRM 60 PWC and SRT 60 PWC cabinets add per-module disconnectors, battery fuse holders and a manual maintenance bypass that isolates all 3 modules.

Batteries

The Sentryum Rack runs on external batteries only: VRLA AGM and GEL, open vented, NiCd, lithium-ion or supercapacitor banks. Charging current is up to 20 A per module; runtime depends on how the external bank is sized.

Industrial environments

Signal and power connections on the module are segregated, which the manufacturer says protects against interference from disturbed industrial grids. The power terminals use front-accessible Harting connectors, described by the manufacturer as protected against dust, humidity and suspended chemical particles. The unit itself is rated IP20, so the installation room should be designed accordingly.

Related services and products

Energom Electronic Kft. is an official distributor of Riello UPS. Energom sizes the module count, redundancy and external battery bank for Sentryum Rack systems, then handles installation, commissioning and scheduled maintenance. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

How many modules can run in parallel in a Sentryum Rack system?

A Sentryum Rack system can run up to 8 modules of 20 kVA/kW in parallel, for a total of 160 kVA/kW. A Sentryum Rack cabinet holds up to 3 modules (60 kVA/kW), and each module needs a parallel kit for parallel operation.

Can a Sentryum Rack module go into an existing 19-inch cabinet?

Yes. The Sentryum Rack SRM 20 and SRT 20 standalone modules mount in a 19-inch cabinet or mounting frame, provided its usable depth and rail load rating are sufficient. A module measures 445 × 664 × 397 mm (9U) and weighs 41 kg; the display can be remoted up to 2 m.

What batteries does the Sentryum Rack use?

The Sentryum Rack runs on external battery banks only: VRLA AGM and GEL, open vented, NiCd, lithium-ion or supercapacitors. The standard string is 20 + 20 × 12 V blocks with a central neutral point; the block count is adjustable from 15 + 15 to 22 + 22.

What supply can the Sentryum Rack connect to?

The Sentryum Rack connects to both single-phase (220 / 230 / 240 V + N) and three-phase (380 / 400 / 415 V + N) inputs; the module detects the arrangement automatically. Input voltage tolerance is ±20% at full load and up to −40% at half load, with a 40–72 Hz frequency range.

Request a quote

For a quote, share the protected load (kVA and kW), the number of output phases, the redundancy requirement, the required runtime and battery technology, and whether the modules go into an existing 19-inch cabinet (with its usable mounting depth) or a Sentryum Rack cabinet.

Request a Quote

We respond within 24 hours on business days.