TAB e.module L5.1 LFP Rack Battery Module, 51.2 V / 5,120 Wh
The TAB e.module L5.1 is a 19-inch rack-mount LiFePO4 (LFP) battery module rated at 51.2 V and 5,120 Wh. The module is designed for residential and small commercial energy storage, backup power and off-grid systems. Up to 32 modules can be connected in parallel (approx. 164 kWh), with CAN and RS485 communication and certification to IEC 62619 and IEC 63056.
Key specifications at a glance
- Nominal rating, cell chemistry: 51.2 V / 5120 Wh; LiFePO4 (LFP)
- Charge/discharge current: 75 A recommended continuous; max 100 A continuous (at 10–35 °C); 200 A peak (15 s)
- Scalability: max 32 modules in parallel (approx. 164 kWh); 6 × 32 modules with TAB LV HUB (approx. 983 kWh); no series connection
- Communication, certification: CAN, RS485; IEC 62619, IEC 63056, UN38.3, CE
- Operating temperature, protection rating: 0–45 °C; IP20
- Compatibility (Energom statement, not manufacturer data): Delta, Vertiv and Eaton telecom power systems
According to Energom, the TAB e.module L5.1 is compatible with Delta, Vertiv and Eaton telecom power systems. This is Energom's own statement, not manufacturer data; we verify the integration for each specific system.
Applications
- Residential energy storage with self-consumption optimization.
- Load shifting and peak shaving.
- Backup power during grid outages.
- Off-grid systems with solar PV.
- Commercial and UPS applications within TAB e.storage systems.
- Telecom backup power (according to Energom).
e.module L series models
The TAB e.storage catalog lists a single model in the e.module L series, so this page covers one module.
| Model | Rating | Key feature |
|---|---|---|
| TAB e.module L5.1 (ID number 1026194) | 51.2 V / 5,120 Wh | 19-inch rack-mount LFP module; max 32 modules in parallel (6 × 32 with TAB LV HUB) |
LFP battery module technical specifications
| Parameter | Value |
|---|---|
| ID number | 1026194 |
| Cell chemistry | LiFePO4 (LFP) |
| Nominal voltage | 51.2 V |
| Nominal energy | 5,120 Wh |
| Charge voltage | 56.8 V DC |
| Discharge cut-off voltage | 44.8 V DC |
| Depth of discharge (DoD) | 97% |
| Charge and discharge current | 75 A recommended continuous; max 100 A continuous at 10–35 °C (lower outside this range); 200 A peak (15 s) |
| Parallel expansion | max 32 modules (approx. 164 kWh); 6 × 32 modules with TAB LV HUB (approx. 983 kWh); no series connection |
| System expansion (TAB FLEXHUB) | multi-cluster architecture, parallel group management, centralized monitoring; real-time monitoring per cluster, unified SoC and SoH management, encrypted communication |
| Battery management system (BMS) | protects the cells against abnormal temperature, current, voltage, SoC and SoH |
| Communication | CAN, RS485 |
| Operating temperature | 0–45 °C |
| Storage temperature | −30 to 45 °C for up to 1 month; −20 to 35 °C for up to 6 months (charge at least every 6 months) |
| Relative humidity | 20–95% (non-condensing) |
| Altitude | max 3,000 m |
| Protection rating | IP20 |
| Dimensions (W × D × H) | 442 × 459 × 160 mm |
| Weight | 47.5 kg |
| Safety and transport | IEC 62619, IEC 63056 (safety); UN38.3 (transport, mandatory for air shipment) |
| Further compliance | IEC 61000 (EMC); Performance Level C per EN 13849-1:2015 |
| CE conformity | electromagnetic compatibility, Low Voltage Directive (LVD) |
| Manufacturing | developed and manufactured at TAB's own facility in Slovenia (EU) |
Source: TAB e.storage catalog, V10_05_2026; TAB e.module L5.1 manufacturer product page, November 2026; TAB e.module L5.1 technical data sheet, June 14, 2024. Specifications are subject to change by the manufacturer.
How to choose
- Energy demand and module count: each module stores 5,120 Wh nominal. Up to 32 modules connect in parallel (approx. 164 kWh); for larger systems, the TAB LV HUB manages 6 clusters of up to 32 modules each (approx. 983 kWh).
- System voltage: the modules cannot be connected in series, so the bank stays at 51.2 V nominal as it grows. Capacity scales with parallel modules; voltage does not.
- Current demand: each module supports 75 A recommended continuous current, up to 100 A at 10–35 °C and 200 A for 15 seconds. Size the number of parallel modules for the load and charging current, not only for the energy requirement.
- Installation environment: the IP20 rating and the 0–45 °C operating range call for an enclosed indoor room. At 47.5 kg per module in a 19-inch rack, check the rack's load rating against the planned module count.
- Communication: the module connects to the controlling equipment over CAN or RS485. Energom verifies protocol matching with the specific inverter or rectifier controller on each project.
Related services and products
- Industrial batteries – the full battery range by technology.
- Battery maintenance – periodic inspection; for LFP batteries, BMS data readout and cell balancing checks.
- DC power systems – DC power design and installation, including telecom applications.
- 48 VDC systems – rectifiers and telecom DC power.
- TAB e.module H10.2 – series-connectable LFP module for commercial and industrial energy storage.
Energom Electronic Kft. is an official distributor of TAB. Services across the Central and Eastern European region; product delivery across Europe. Energom handles sizing of the e.module L5.1 battery bank, matches the module count and the communication link to the connected system, and performs installation, commissioning and periodic maintenance.
FAQ
How many TAB e.module L5.1 modules can be connected?
Up to 32 TAB e.module L5.1 modules can be connected in parallel, for approx. 164 kWh. With the TAB LV HUB, a system of 6 × 32 modules (approx. 983 kWh) is possible; the modules cannot be connected in series.
What is the charge and discharge current of the TAB e.module L5.1?
The TAB e.module L5.1 recommended continuous charge and discharge current is 75 A, the maximum continuous current is 100 A at 10–35 °C, and the peak current is 200 A for 15 seconds. Outside the 10–35 °C range, the permitted continuous current is lower.
Which certifications does the e.module L5.1 have?
According to TAB, the module meets IEC 62619 and IEC 63056 for safety and UN38.3 for transport. The CE marking covers electromagnetic compatibility and the Low Voltage Directive; TAB also lists IEC 61000 (EMC) and Performance Level C per EN 13849-1:2015.
How should the e.module L5.1 be stored before commissioning?
Per the TAB data sheet, the module can be stored at −30 to 45 °C for up to 1 month or at −20 to 35 °C for up to 6 months, and it must be charged at least every 6 months. Relative humidity may range from 20% to 95%, non-condensing.
Can the TAB e.module L5.1 be connected in series?
The TAB e.module L5.1 documents describe parallel expansion only: up to 32 modules (approx. 164 kWh), or 6 × 32 modules with the TAB LV HUB. The bank therefore stays at 51.2 V nominal as it grows, and capacity increases with the number of parallel modules.
Request a quote
When requesting a quote, include the type of system the battery will support (inverter, rectifier or UPS), the load current, the required energy or backup time, your communication requirements and the room temperature at the installation site.
We respond within 24 hours on business days.