Key specifications at a glance

  • Nominal rating, cell chemistry: module: 51.2 V / 100 Ah / 5.12 kWh, LFP; system (HV48100): 5–15 modules in series, 256–768 V, 25.6–76.8 kWh
  • Cycle life: ≥6000 cycles (0.5C, 25 °C, 90% DoD, 70% end-of-life capacity) – HV48100 SE
  • Charge/discharge current: 50 A continuous per string
  • Scalability: HV48100 SE: max 3 cabinets (2P configuration) or 6 cabinets (1P configuration) per inverter
  • Communication, certification: CAN, RS485, dry contact; CE, IEC 62619 (for the battery system), UN38.3 – HV48100; HV48100 SE: we check the certified configuration with the manufacturer when quoting
  • Protection rating, temperature: HV48100: IP20, charge 0–45 °C, discharge −10–50 °C; HV48100 SE: IP55, −20 to +50 °C, 2 kW air conditioner

Applications

  • Commercial and industrial (C&I) energy storage.
  • Public and commercial facilities – for the HV48100 SE, Pytes names hospitals, schools, agricultural sites and shopping malls.
  • Outdoor installation in an air-conditioned IP55 cabinet (HV48100 SE).

Pytes HV48100 models

The indoor HV48100 comes in three cabinet sizes depending on module count; the outdoor HV48100 SE holds 3–15 modules in a single cabinet, with four configurations detailed by the manufacturer.

Pytes HV48100 models
Model Modules and energy Distinguishing feature
HV48100 8S (indoor) 5–8 modules (25.6–40.96 kWh) cabinet 600 × 640 × 1,555 mm; cabinet weight 89.6 kg (excluding modules); IP20
HV48100 12S (indoor) 9–12 modules (46.08–61.44 kWh) cabinet 595 × 680 × 2,100 mm; cabinet weight 138 kg (excluding modules); IP20
HV48100 15S (indoor) 13–15 modules (66.56–76.8 kWh) cabinet 1,054 × 626 × 1,463 mm; cabinet weight 126.5 kg (excluding modules); IP20
HV48100 SE (outdoor) 3–15 modules; detailed configurations 61.44–76.8 kWh IP55, 2 kW air conditioner, 5-layer fire protection system

HV48100 SE detailed configurations

Pytes HV48100 models
Configuration Rated energy Rated power Operating voltage Charge/discharge current Rated capacity Weight
2P6S 61.44 kWh 30.72 kW 273–341 V 2 × 50 A 2 × 100 Ah 1,013 kg
2P7S 71.68 kWh 35.84 kW 318–398 V 2 × 50 A 2 × 100 Ah 1,106 kg
1P12S 61.44 kWh 30.72 kW 546–682 V 50 A 100 Ah 999 kg
1P15S 76.8 kWh 38.4 kW 683–852 V 50 A 100 Ah 1,139 kg

Up to 3 cabinets can be connected per inverter in the 2P configuration, and up to 6 cabinets in the 1P configuration.

High-voltage LiFePO4 battery specifications

High-voltage LiFePO4 battery specifications
Parameter HV48100 (indoor) HV48100 SE (outdoor)
Module (BMU) rating 51.2 V / 100 Ah / 5.12 kWh, LFP 51.2 V / 100 Ah / 5.12 kWh, LFP
Module voltage range 45.5–58 V see the configuration table above
Module depth of discharge (DoD) 90% 90%
Module charge/discharge current 50 A continuous 50 A rated and max
Modules per system 5–15, in series 3–15
System nominal voltage 256–768 V (5–15 modules × 51.2 V) by configuration, see the table above
System working voltage range (BCU) 200–870 V 142.5–864 V
Cycle life – ≥6,000 cycles (0.5C, 25 °C, 90% DoD, 70% end-of-life capacity)
Module operating temperature charge 0–45 °C; discharge −10–50 °C charge 0–55 °C; discharge −10–55 °C
Cabinet operating temperature – −20 to +50 °C
Module storage temperature within 1 month −20 to 50 °C; 1–3 months −10 to 40 °C; 3–12 months 0 to 30 °C –
Module dimensions and weight 484 × 530 × 140 mm; 43 kg 484 × 530 × 140 mm; 45.16 kg
Battery control unit (BCU) self-consumption 7.56 W; 484 × 510 × 140 mm; 13.3 kg self-consumption 7.56 W; 484 × 510 × 140 mm; 13.6 kg; IP20
External communication (BCU) CAN, RS485, dry contact, WiFi CAN, RS485, dry contact
Internal communication RS232 RS232 (monitoring); battery side: CAN, RS485
Cabinet 8S, 12S, 15S versions (see models table); IP20 1,100 × 1,193 × 2,015 mm (W × D × H); 999–1,139 kg depending on configuration; IP55
Cooling – air cooling; factory-installed 2 kW air conditioner with R134a refrigerant; heating pad and cooling fan in each module
Fire protection – 5-layer: heat, smoke and gas detectors; exhaust and ventilation system; aerosol fire suppression; explosion relief plate; water firefighting port
Monitoring – current, voltage and temperature monitoring at cell, module and system level; short-circuit protection
Relative humidity – 0–95% (non-condensing)
Operating altitude – max 3,000 m
Certification CE, IEC 62619 (for the battery system), UN38.3 CE, IEC 62619 (for the battery system), UN38.3; we check the certified configuration with the manufacturer when quoting

Source: Pytes energy storage catalog, 2026 V1.1. Specifications are subject to change by the manufacturer.

How to choose

How to choose
Situation Recommended model Why
Indoor mechanical or electrical room HV48100 (8S, 12S or 15S cabinet) IP20 cabinet sized to the module count
Outdoor installation HV48100 SE IP55 cabinet, built-in 2 kW air conditioner and 5-layer fire protection
61.44 kWh in one cabinet for a lower system-voltage inverter HV48100 SE 2P6S two parallel strings, 273–341 V operating voltage, 2 × 50 A
71.68 kWh in one cabinet for a lower system-voltage inverter HV48100 SE 2P7S two parallel strings, 318–398 V operating voltage, 2 × 50 A
61.44 kWh in one cabinet for a higher system-voltage inverter HV48100 SE 1P12S single string, 546–682 V operating voltage, 50 A
76.8 kWh in one cabinet for a higher system-voltage inverter HV48100 SE 1P15S single string, 683–852 V operating voltage, 50 A
  • Inverter voltage window: the number of series-connected modules sets the system voltage, so choose the configuration to match the inverter's battery voltage range.
  • Power: each string supplies 50 A continuous; the HV48100 SE in the 2P configuration delivers 2 × 50 A.
  • Expansion: up to 3 HV48100 SE cabinets (2P) or 6 cabinets (1P) can be connected per inverter.
  • Site preparation: the outdoor cabinet has a 1,100 × 1,193 mm footprint and weighs 999–1,139 kg depending on configuration; plan the foundation and delivery route accordingly. For the indoor system, add 43 kg per module to the cabinet weight; the BCU weighs 13.3 kg.

Related services and products

Energom Electronic Kft. is an official distributor of Pytes. Services across the Central and Eastern European region; product delivery across Europe. Energom sizes the battery system, matches the configuration to the inverter, and handles installation, commissioning and periodic maintenance.

FAQ

Can the Pytes HV48100 be installed outdoors?

The HV48100 SE is the outdoor version: an IP55 cabinet with a factory-installed 2 kW air conditioner and an operating temperature of −20 to +50 °C. The indoor HV48100 cabinets are rated IP20.

How many modules make up an HV48100 system?

The indoor HV48100 uses 5–15 series-connected modules, for 25.6–76.8 kWh of nominal energy. The HV48100 SE is configurable with 3–15 modules per system; the manufacturer details four configurations between 61.44 and 76.8 kWh.

How many HV48100 SE cabinets can connect to one inverter?

According to the manufacturer's catalog, up to 3 Pytes HV48100 SE cabinets can be connected per inverter in the 2P configuration, and up to 6 cabinets in the 1P configuration.

What fire protection does the HV48100 SE have?

The Pytes HV48100 SE cabinet has a 5-layer fire protection system: heat, smoke and gas detectors; an exhaust and ventilation system; aerosol fire suppression; an explosion relief plate; and a water firefighting port.

Request a quote

When requesting a quote, include the inverter model and its battery voltage range, the required stored energy (kWh) and power (kW), the installation site (indoor or outdoor) and any planned expansion.

Request a Quote

We respond within 24 hours on business days.

Request a Callback