Key specifications at a glance

  • Power, energy: 105 kW / 232.96 kWh (230EX); 125 kW, max 138 kVA / 261 kWh (261EX); 400 V, 3-phase + N
  • Cells, cooling: LFP (261EX: 314 Ah); liquid cooling
  • Cycle life (261EX): 6,000 cycles (20–35 °C, 0.5P/0.5P, 90% DoD, 70% end-of-life capacity)
  • Compliance: 261EX: EN 50549-1/-2/-10, VDE-AR-N 4105 / 4110, cell: IEC 62619, UN 38.3; 230EX system: IEC 62619, IEC 63056, IEC 62477, UN38.3
  • Protection rating, fire protection: IP55; aerosol suppression, water connection, heat, smoke and gas sensing

Applications

  • Peak shaving, valley filling and peak-to-valley arbitrage at commercial and industrial sites.
  • Demand management.
  • Grid connection and transformer capacity relief.
  • Standby power supply (with the optional backup module).
  • Frequency regulation (a manufacturer-listed function; market participation is subject to separate requirements).
  • Energy storage at distribution grid and renewable generation sites.

Pi Station models: outdoor C&I energy storage cabinets

Pi Station models: outdoor C&I energy storage cabinets
Model Rating Distinguishing feature
Pi Station 230EX 105 kW / 232.96 kWh recommended charge and discharge current 140 A
Pi Station 261EX 125 kW (max 138 kVA) / 261 kWh recommended charge and discharge current 157 A; country-specific grid code listings, including Hungary

Technical specifications

Technical specifications
Parameter Pi Station 230EX Pi Station 261EX
Rated power 105 kW 125 kW, max 138 kVA
Rated energy 232.96 kWh 261 kWh
Grid connection 400 V AC, 3-phase + N (3P4W) 400 V AC, 3-phase + N (3P4W); 50/60 Hz
Battery nominal voltage 832 V 832 V
Operating DC voltage range 650–949 V 650–949 V
Recommended charge and discharge current 140 A 157 A
Current derating below 0 °C and above 45 °C below 0 °C and above 45 °C
Depth of discharge (DoD) – 90%
Cell chemistry LFP LFP, 314 Ah
Battery configuration not published by the manufacturer system 260S1P; liquid-cooled pack 1P52S, 314 Ah, 166.4 V, 333 ± 5 kg, IP67
Cycle life – 6,000 cycles (20–35 °C, 0.5P/0.5P, 90% DoD, 70% end-of-life capacity)
Cooling liquid cooling liquid cooling and dehumidification
Protection rating IP55 IP55
Fire protection aerosol suppression, water connection, heat, smoke and gas sensing aerosol suppression, water connection, heat, smoke and gas sensing
Communication CAN, RS485, Ethernet; Modbus RTU/TCP CAN, RS485, Ethernet; Modbus RTU/TCP; industrial display
Dimensions (W × D × H) 1000 × 1390 × 2430 mm 1000 × 1390 × 2430 mm
Weight 2,500 kg 2,500 kg
Operating temperature −20 to +55 °C −20 to +55 °C
Recommended cell temperature charge 0–55 °C; discharge −20 to +55 °C charge 0–55 °C; discharge −20 to +55 °C
Humidity, altitude 0–95%, non-condensing; 2,000 m, derating above 0–95%, non-condensing; 2,000 m, derating above
Installation outdoor-rated; back-to-back parallel installation; optional backup module outdoor-rated; back-to-back parallel installation; optional backup module
Grid compliance (PCS) CE-EMC, CE-LVD; EN 50549-1 and EN 50549-2 (European general); EN 50549-1 C10/11 (Belgium); EN 50549-1 (Netherlands, Greece, Sweden, Poland); VDE-AR-N 4105:2018 EN 50549-1/-2/-10; Hungary: EN 50549-2 (listed by the manufacturer as “50549-2 + Hungary”); Germany: VDE-AR-N 4105, 4110, 4120; Italy: CEI 0-21, CEI 0-16; Austria: TOR EZA Type A and B; Belgium: C10/11; Poland: PN-EN 50549-2; Spain: UNE 217001, UNE 217002, NTS 631 (listed by the manufacturer as “217001, 217002, NTS631”); also Czech Republic, Romania, Slovenia, Bulgaria and further EU countries; CE-LVD (IEC 62477, IEC 62109), CE-EMC (IEC 61000)
System and cell compliance system: IEC 62619, IEC 63056, IEC 62477, UN38.3 cell: IEC 62619, UN 38.3

Source: Pytes Pi Station 261 EX datasheet (September 16, 2026), Pi Station 261EX user manual (V1.0, May 25, 2026), Pytes product catalog (2026, V1.1) and Pytes EU product page (November 2026). Specifications are subject to change by the manufacturer.

How to choose

Power and energy

The Pi Station 230EX is rated 105 kW / 232.96 kWh and the Pi Station 261EX 125 kW (max 138 kVA) / 261 kWh. Model selection follows from the peak power to be shaved and the energy to be shifted per discharge cycle; according to Pytes, cabinets can be installed back to back in parallel; multi-cabinet systems are engineered case by case.

Grid connection in Hungary

The manufacturer's grid compliance list for the Pi Station 261EX names Hungary explicitly (EN 50549-2, listed as “50549-2 + Hungary”), alongside German VDE-AR-N 4110 and 4120. For the 230EX, Pytes lists general European compliance (EN 50549-1, EN 50549-2) and VDE-AR-N 4105:2018. Energom coordinates the manufacturer documentation needed for grid connection approval on each project.

Site and foundation

Both models are outdoor cabinets measuring 1000 × 1390 × 2430 mm and weighing 2,500 kg; the installation area and foundation must be designed accordingly. The cabinet operates from −20 to +55 °C, with derating above 2,000 m altitude.

Temperature and loading

The recommended charge and discharge current is 140 A (230EX) or 157 A (261EX); below 0 °C and above 45 °C, the system derates current. Liquid cooling controls cell temperature; on the Pi Station 261EX, a dehumidifier controls humidity inside the cabinet.

Backup and control

An optional backup module is available for standby power supply. The cabinet connects to an energy management system (EMS) over CAN, RS485 and Ethernet using Modbus RTU/TCP.

Related services and products

Energom Electronic Kft. is an official distributor of Pytes. Services across the Central and Eastern European region; product delivery across Europe. Energom sizes the Pi Station system from the site load profile and grid connection data, and handles installation, commissioning, EMS integration and ongoing maintenance.

FAQ

Does the Pytes Pi Station meet Hungarian grid connection requirements?

The manufacturer's compliance list for the Pi Station 261EX names Hungary explicitly, tied to EN 50549-2. For the Pi Station 230EX, Pytes lists general European compliance (EN 50549-1, EN 50549-2) without naming Hungary. Connection terms are set in every case by the distribution system operator's approval process.

What is the cycle life of the Pi Station 261EX?

For the Pi Station 261EX, Pytes specifies 6,000 cycles at 20–35 °C, with 0.5P charge and discharge, 90% depth of discharge and 70% end-of-life capacity. Cycle data for the Pi Station 230EX is confirmed with the quote.

What fire protection does the Pi Station have?

The Pytes Pi Station cabinet has an aerosol suppression system, a water connection and heat, smoke and gas sensing, with an IP55 enclosure rating. The liquid-cooled battery packs of the Pi Station 261EX are IP67-rated.

Can the Pi Station be installed outdoors?

Both Pytes Pi Station models are outdoor cabinets rated IP55, operating from −20 to +55 °C at 0–95% non-condensing humidity. The rated installation altitude is 2,000 m, with derating above.

How does the Pi Station integrate with an energy management system?

The cabinet provides CAN, RS485 and Ethernet interfaces with Modbus RTU/TCP; the Pi Station 261EX also has an industrial display.