Key specifications at a glance

  • Technology: pure lead AGM VRLA, thin plate
  • Nominal rating: 12 V; 370–530 W/cell (15 min, 1.67 V/cell, 25 °C); 78–120 Ah (C10, 1.80 V/cell, 25 °C); top-terminal W models
  • Design life: Eurobat Very Long Life (>12 years)
  • Terminal: top, M8 female; front-access version for 19″/23″ cabinets
  • Standards: IEC 60896-21 and -22
  • Container: flame-retardant ABS, UL94 V-0

Applications

  • Data centers – as the battery bank of UPS systems.
  • UPS systems – the main application of the top-terminal FPG according to the FIAMM engineering manual.
  • Telecom – backup power at telecom sites; a secondary application per the FIAMM engineering manual.
  • Industry and utilities – a secondary application per the FIAMM engineering manual.

Pure Guard (FPG) models

Pure Guard (FPG) models
Model Nominal power (15 min, 1.67 V/cell, 25 °C) Nominal capacity (C10, 1.80 V/cell, 25 °C) Distinguishing feature
FPG360W 370 W/cell 78 Ah 261 mm long, 26.8 kg
FPG410W 430 W/cell 88 Ah 302 mm long, 30.5 kg
FPG460W 475 W/cell 105 Ah 341 mm long, 33.8 kg
FPG510W 530 W/cell 120 Ah 379 mm long, 37.5 kg

All four models are 12 V blocks sharing the same 174 mm width and 217 mm height; they differ in length and weight. The model table and specifications cover the top-terminal W models; data for the front-terminal version is provided on request.

Technical specifications – FPG VRLA AGM battery

Technical specifications – FPG VRLA AGM battery
Parameter Value
Nominal voltage 12 V
Positive plate pure lead positive grid, flat pasted plates
Electrolyte sulfuric acid, specific gravity 1.3 at 20 °C, absorbed in glass microfiber (AGM) separators
Dimensions (length × width × height) FPG360W: 261 × 174 × 217 mm; FPG410W: 302 × 174 × 217 mm; FPG460W: 341 × 174 × 217 mm; FPG510W: 379 × 174 × 217 mm
Weight (typical) FPG360W: 26.8 kg; FPG410W: 30.5 kg; FPG460W: 33.8 kg; FPG510W: 37.5 kg
Terminal torque M8 top terminal: 10–12 Nm
Recommended float voltage 2.27 V/cell at 20 °C; temperature compensation: −2.5 mV/cell/°C (between −20 and +50 °C)
Typical float current approx. 0.3 mA/Ah (fully charged, 2.27 V/cell, 20 °C)
Boost (equalizing) charge 2.40 V/cell at 20 °C, max current limit 0.25 C10; stop at 0.001 C10 charging current or after 24 hours; recommended every 12 months
Recommended operating temperature 10–30 °C; operable from −20 to +50 °C, with reduced life expectancy above 20 °C
End-of-life criterion below 80% of nominal capacity
Gas recombination efficiency >98%
Safety valve opening pressure 0.15–0.30 atm (15–30 kPa)
Storage without refresh charge 24 months at 20 °C; 12 months at 30 °C; 6 months at 40 °C; refresh charge at the latest when the open-circuit voltage falls to 2.09 V/cell
Optimal storage conditions −10 to +30 °C, max 90% relative humidity
Parallel strings typically 4 (more depending on string voltage and cable length)
Maintenance no water topping-up required (VRLA); battery condition (voltage, temperature, internal resistance, valve) must still be checked periodically per the manufacturer's instructions
Transport non-hazardous per the manufacturer's classification; transportable by road, rail or air
Recyclability 99% recyclable at end of life
Standards IEC 60896-21, IEC 60896-22, IEC 62485-2, IEC 60695-11-10, BS 6290-4, BS 6290-1
Case material flammability rating V-0 (UL 94 material test; BS 6334)

Source: FIAMM Pure Guard (FPG) brochure, Rev. 04.2026; FIAMM Pure Lead AGM engineering manual, edition 07/2026, Rev.02 (charging, temperature and storage data apply to the entire Pure Lead AGM range). Specifications are subject to change by the manufacturer.

How to choose

Power demand over the discharge time

In UPS applications, sizing starts from the power per cell required for the specified backup time. The model table gives 15-minute values to 1.67 V/cell, from 370 W/cell (FPG360W) up to 530 W/cell (FPG510W); the actual configuration is calculated from the UPS DC bus voltage, the load and the required runtime.

Footprint and weight

All four models share the same 174 × 217 mm cross-section, so in a given cabinet height a longer, higher-capacity block delivers more energy. Weight rises from 26.8 kg to 37.5 kg, which matters for rack and floor loading.

Terminal and cabinet

The W models have top-mounted M8 female terminals. If the installation calls for front access in a 19-inch or 23-inch cabinet, note the front-terminal version in your quote request.

Operating environment and charging

FIAMM recommends an operating temperature of 10–30 °C; above 20 °C, life expectancy is reduced. Set the UPS charger to a float voltage of 2.27 V/cell (20 °C) with −2.5 mV/cell/°C temperature compensation.

How to choose
Situation Recommended model Why
Smaller UPS rating, limited shelf length FPG360W 370 W/cell, 261 mm long
Mid-range power demand FPG410W or FPG460W 430 or 475 W/cell
Highest power per cell from a single block FPG510W 530 W/cell, 120 Ah (C10)

Related services and products

Energom Electronic Kft. is an official distributor of FIAMM. Energom sizes FPG battery banks to the UPS rating and the required backup time, handles installation and commissioning, and tracks battery condition through capacity testing. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

What does pure lead technology mean in the FPG battery?

According to the FIAMM engineering manual, the FPG uses a pure lead positive grid with flat pasted, thin plates. The thin-plate design targets short, high-power discharges typical of UPS applications.

What float voltage does the FIAMM FPG require?

For the FIAMM FPG, FIAMM specifies a float voltage of 2.27 V/cell at 20 °C with −2.5 mV/cell/°C temperature compensation. The boost charge is 2.40 V/cell (20 °C) with a max current limit of 0.25 C10.

How long can FPG batteries be stored without recharging?

Per the FIAMM Pure Lead engineering manual, FIAMM FPG blocks can be stored without recharging for up to 24 months at 20 °C, 12 months at 30 °C and 6 months at 40 °C. A refresh charge is due at the latest when the open-circuit voltage falls to 2.09 V/cell.

How many FPG strings can be connected in parallel?

For the FIAMM FPG, FIAMM typically specifies 4 parallel strings; more are possible depending on string voltage and cable length, which is verified during the design of the specific battery bank.

What is the design life of the FPG?

The FIAMM FPG carries a Eurobat Very Long Life (>12 years) classification. FIAMM defines end of life as capacity falling below 80% of the nominal value; at operating temperatures above 20 °C, life expectancy is shorter. Design life is a design figure, not a guaranteed service life; actual service life depends on operating temperature, charger settings and discharge frequency.

Request a quote

For an accurate quote, include the UPS model and rating, the DC bus voltage, the required backup time and the installation location (rack or cabinet, top or front terminals).