FIAMM FLB 12 V, 24–200 Ah High-Rate VRLA AGM Battery
The FIAMM FLB is a 12 V high-rate VRLA AGM battery block range rated 24–200 Ah (C10, 1.80 V/cell, 25 °C) and 103–710 W/cell (15 min, 1.67 V/cell, 25 °C). FIAMM designed the FLB for the high-rate, short-duration discharge of UPS systems and data centers; the FLB is available with top or front terminals in a flame-retardant ABS container.
Key specifications at a glance
- Technology: AGM VRLA, high rate
- Nominal rating: 12 V; 103–710 W/cell (15 min, 1.67 V/cell, 25 °C); 24–200 Ah (C10, 1.80 V/cell, 25 °C)
- Design life: Eurobat Long Life (10/12 years) for top-terminal models, Very Long Life (>12 years) for front-terminal models
- Terminal: top or front design; M5, M6 or M8 thread, model dependent
- Standards: IEC 60896-21 and -22
- Container: flame-retardant ABS, UL94 V-0
Applications
- UPS backup power – battery banks for short-duration, high-power discharge.
- Data centers – as the battery bank of UPS systems; a main application per the FIAMM AGM engineering manual.
- Telecom – a secondary application per the FIAMM AGM engineering manual.
- Industry and utilities – a secondary application per the engineering manual.
- Motion applications (FIAMM's Motion application category) – a secondary application per the engineering manual.
FLB models
| Model | Nominal power (15 min, 1.67 V/cell, 25 °C) | Capacity C10 (1.80 V/cell, 25 °C) | Capacity C20 (1.75 V/cell, 25 °C) | Weight (typical) |
|---|---|---|---|---|
| 12FLB100P | 103 W/cell | 24 Ah | 26 Ah | 8.5 kg |
| 12FLB150P | 156 W/cell | 44 Ah | 48 Ah | 14 kg |
| 12FLB200P | 204 W/cell | 53 Ah | 57 Ah | 17 kg |
| 12FLB250P | 257 W/cell | 75 Ah | 80 Ah | 24 kg |
| 12FLB300P | 311 W/cell | 78 Ah | 84 Ah | 26 kg |
| 12FLB350P | 374 W/cell | 90 Ah | 95 Ah | 30 kg |
| 12FLB400P | 415 W/cell | 101 Ah | 109 Ah | 34 kg |
| 12FLB450P | 477 W/cell | 115 Ah | 124 Ah | 38 kg |
| 12FLB540P | 540 W/cell | 140 Ah | 150 Ah | 49 kg |
| 12FLB700P | 710 W/cell | 200 Ah | 216 Ah | 61 kg |
All models are 12 V blocks. Terminal design (top or front) and thread size depend on the model; specify the required design in your quote request.
Technical specifications – FLB VRLA AGM battery
| Parameter | Value |
|---|---|
| Nominal voltage | 12 V |
| Electrolyte | sulfuric acid, specific gravity 1.3 at 20 °C, absorbed in glass microfiber (AGM) separators |
| Dimensions (brochure column order: Length × Width × Height) | 12FLB100P: 166 × 175 × 126 mm; 12FLB150P: 198 × 166 × 170 mm; 12FLB200P: 230 × 140 × 212 mm; 12FLB250P: 260 × 168 × 214 mm; 12FLB300P: 261 × 174 × 217 mm; 12FLB350P: 302 × 174 × 217 mm; 12FLB400P: 341 × 174 × 217 mm; 12FLB450P: 379 × 174 × 217 mm; 12FLB540P: 338 × 174 × 277 mm; 12FLB700P: 531 × 126 × 321 mm |
| Terminal torque | M5: 5–6 Nm; M6: 7–9 Nm; M8: 10–12 Nm (by thread size) |
| Recommended float voltage | 2.27 V/cell at 20 °C; temperature compensation: −2.5 mV/cell/°C (between −20 and +50 °C) |
| Typical float current | approx. 0.6 mA/Ah (fully charged, 2.27 V/cell, 20 °C) |
| Boost (equalizing) charge | 2.40 V/cell at 20 °C, max current limit 0.25 C10; stop at 0.001 C10 charging current or after 24 hours; recommended every 12 months |
| Recommended operating temperature | 10–30 °C; operable from −20 to +50 °C, with reduced life expectancy above 20 °C |
| End-of-life criterion | below 80% of nominal capacity |
| Gas recombination efficiency | >98% |
| Safety valve opening pressure | 0.15–0.30 atm (15–30 kPa) |
| Storage without refresh charge | 9 months at 20 °C; 6 months at 30 °C; 3 months at 40 °C; refresh charge at the latest when the open-circuit voltage falls to 2.09 V/cell |
| Optimal storage conditions | −10 to +30 °C, max 90% relative humidity |
| Parallel strings | typically 4 (more depending on string voltage and cable length) |
| Remote venting system (RVS) | optional accessory, top-side, for installation in enclosed cabinets (does not replace ventilation) |
| Maintenance | no water topping-up required (VRLA); battery condition (voltage, temperature, internal resistance, valve) must still be checked periodically per the manufacturer's instructions |
| Transport | non-hazardous per the manufacturer's classification; transportable by road, rail or air |
| Recyclability | 99% recyclable at end of life |
| Standards | IEC 60896-21, IEC 60896-22, IEC 62485-2, IEC 60695-11-10, BS 6290-4, BS 6290-1 |
| Case material flammability rating | V-0 (UL 94 material test; BS 6334) |
Dimensions are listed in the brochure's Length × Width × Height column order; refer to the manufacturer's dimensional drawing for mounting orientation.
Source: FIAMM FLB brochure, Rev. 04.2026; FIAMM AGM (VRLA) engineering manual, edition 07/2026, Rev.16 (charging, temperature and storage data apply to the entire FIAMM AGM range). Specifications are subject to change by the manufacturer.
How to choose
Power over the discharge time
FLB sizing starts from the power per cell required for the UPS backup time. The model table gives 15-minute values to 1.67 V/cell, from 103 W/cell (12FLB100P) up to 710 W/cell (12FLB700P), so the range has a block size for both small and large UPS systems.
Capacity and its test condition
The brochure states FLB capacity under two conditions: C10 (1.80 V/cell) and C20 (1.75 V/cell), both at 25 °C. The same block shows a higher figure at C20 (for example, 12FLB400P: 101 Ah at C10, 109 Ah at C20), so always compare models using values measured under the same condition.
Terminal design and design life
Top-terminal models carry a Eurobat Long Life (10/12 years) classification and front-terminal models a Very Long Life (>12 years) classification. If the string requires front-access terminals, note this in your quote request.
Installation environment
Ventilation is mandatory in enclosed cabinets as well and must be sized per IEC 62485-2, which FIAMM lists as an applicable standard. An optional top-side remote venting system (RVS) is available as an add-on; it does not replace the sized ventilation, which is still required when an RVS is used. FIAMM recommends an operating temperature of 10–30 °C; above 20 °C, life expectancy is reduced.
| Situation | Recommended model | Why |
|---|---|---|
| Small UPS, limited space | 12FLB100P–12FLB200P | 103–204 W/cell, 8.5–17 kg |
| Mid-size UPS | 12FLB250P–12FLB450P | 257–477 W/cell |
| High-power UPS, fewer parallel strings | 12FLB540P or 12FLB700P | 540 or 710 W/cell |
Related services and products
- Industrial batteries – the full industrial battery portfolio
- Battery maintenance – capacity testing, condition assessment and replacement planning
- Uninterruptible power supply – UPS system design with battery banks
- UPS systems
- FIAMM Pure Guard (FPG)
- FIAMM FIT
- FIAMM SMG OPzV
Energom Electronic Kft. is an official distributor of FIAMM. Energom sizes FLB battery banks to the UPS rating and backup time, handles installation and commissioning, and tracks battery condition through capacity testing. Services across the Central and Eastern European region; product delivery across Europe.
FAQ
What is the difference between the FLB C10 and C20 capacity ratings?
The FIAMM FLB C10 rating refers to a 10-hour discharge to 1.80 V/cell, the C20 rating to a 20-hour discharge to 1.75 V/cell, both at 25 °C. The longer discharge and lower end voltage give a higher C20 figure, for example 216 Ah instead of 200 Ah for the 12FLB700P.
What float voltage does the FIAMM FLB require?
For the FIAMM FLB, the FIAMM AGM engineering manual specifies a float voltage of 2.27 V/cell at 20 °C with −2.5 mV/cell/°C temperature compensation. When fully charged, the typical float current is approx. 0.6 mA/Ah.
How long can FLB batteries be stored without recharging?
Per the FIAMM AGM engineering manual, FIAMM FLB blocks can be stored without recharging for up to 9 months at 20 °C, 6 months at 30 °C and 3 months at 40 °C. A refresh charge is due at the latest when the open-circuit voltage falls to 2.09 V/cell.
What is the design life of the FLB?
Top-terminal FLB models carry a Eurobat Long Life (10/12 years) classification and front-terminal models a Very Long Life (>12 years) classification. FIAMM defines end of life as capacity below 80% of the nominal value; at operating temperatures above 20 °C, life expectancy is shorter. Design life is a design figure, not a guaranteed service life; actual service life depends on operating temperature, charger settings and discharge frequency.