Key specifications at a glance

  • Rated power: 3.7 kW (single-phase) / 11 kW (three-phase) for the 16 A version, 7.4 kW / 22 kW for the 32 A version; 230/400 V
  • Connector: Type 2 cable (5 m); the 32 A version also with Type 2 socket or socket with shutter
  • OCPP: 1.6 (tested with OCTT), AC MAX Smart only; AC MAX Basic has no OCPP
  • Energy management: Modbus TCP (Smart, LAN); Modbus RTU over RS485 (Basic); max charging current set by 8-step DIP switch
  • Protection rating: IP55 / IK09

Applications

  • Commercial buildings: charging in the site's own parking area, with a CPMS connection (AC MAX Smart) or stand-alone.
  • Parking facilities and distributed parking spaces: multiple charge points on single-phase or three-phase supply.
  • Residential areas and home charging: 3.7 or 7.4 kW on a single-phase connection, 11 or 22 kW on three-phase.
  • Indoor and outdoor installation: IP55 / IK09 protection, −30 °C to +50 °C operating temperature.

Delta AC MAX models

Delta AC MAX models
Model Rated power Distinguishing features
AC MAX Basic 3.7/11 kW (16 A) 3.7 kW (single-phase) / 11 kW (three-phase) Key switch, Modbus RTU (RS485), no OCPP; Type 2 cable
AC MAX Basic 7.4/22 kW (32 A) 7.4 kW (single-phase) / 22 kW (three-phase) Key switch, Modbus RTU (RS485), no OCPP; Type 2 cable, Type 2 socket or socket with shutter
AC MAX Smart 3.7/11 kW (16 A) 3.7 kW (single-phase) / 11 kW (three-phase) RFID, LAN, WLAN and cellular, OCPP 1.6, Modbus TCP; Type 2 cable
AC MAX Smart 7.4/22 kW (32 A) 7.4 kW (single-phase) / 22 kW (three-phase) RFID, LAN, WLAN and cellular, OCPP 1.6, Modbus TCP; Type 2 cable, Type 2 socket or socket with shutter

AC EV charging station technical specifications

AC EV charging station technical specifications
Parameter Value
Rated power 3.7 kW (single-phase) / 11 kW (three-phase) for the 16 A version, 7.4 kW / 22 kW for the 32 A version
Grid connection Single-phase (L1, N, PE) or three-phase (L1, L2, L3, N, PE)
AC voltage 230/400 V
Grid frequency 50 Hz / 60 Hz
Grounding systems TN, TT, IT
Nominal input current 16 A (3.7/11 kW version); 32 A (7.4/22 kW version)
Nominal output current 16 A per phase (3.7/11 kW); 32 A per phase (7.4/22 kW)
Input protection Overcurrent, undervoltage, overvoltage, overtemperature, surge protection, short circuit, ground fault
Residual current protection RCD Type A (AC 30 mA), RDC-DD (DC 6 mA)
Standby power 3.6 W (AC MAX Basic); < 10 W (AC MAX Smart)
Connector Type 2 cable (5 m); the 32 A version also with Type 2 socket or socket with shutter
Charging output compliance IEC 61851-1, IEC 62196-2, IEC 61008-1, IEC 62955
Display Status LED, 4 colors
Authentication Key switch (AC MAX Basic); RFID (AC MAX Smart)
Max charging current setting 8-step DIP switch
Bluetooth Configuration, control, monitoring and firmware update
Local area network Ethernet (RJ45) and WLAN (AC MAX Smart)
Cellular connectivity 2G / 3G / 4G, Micro-SIM (AC MAX Smart)
Back-end connection OCPP 1.6, tested with OCTT (AC MAX Smart only)
Energy management interface Modbus TCP (AC MAX Smart, LAN); Modbus RTU over RS485 (AC MAX Basic)
Over-the-air (OTA) firmware update Via Bluetooth (AC MAX Basic); via Wi-Fi (AC MAX Smart)
Cooling Natural convection
Dimensions (W × H × D) 218 × 371 × 167 mm (depending on configuration)
Weight 6.0 kg including charging cable (depending on configuration)
Mounting Wall-mounted or optional pedestal (AC MAX Basic)
Protection rating IP55 (IEC 60529), IK09 (IEC 62262)
Operating temperature −30 °C to +50 °C
Storage temperature −40 °C to +80 °C
Relative humidity < 95%, non-condensing
Altitude max 2,000 m
EU Low Voltage Directive IEC 61851-1, IEC 62479
EU EMC Directive EN 61000-3-11 and -12, IEC 61851-21-2

Source: Delta Electronics manufacturer product pages (AC MAX Basic and AC MAX Smart, en-GB) and the specification tables published on them, March 2024. Specifications are subject to change by the manufacturer.

How to choose

Back-end connection and authentication

If charging is managed by a charge point management system (CPMS) for user access, charging records and remote monitoring, the AC MAX Smart is the right version: RFID authentication, OCPP 1.6 tested with OCTT, and Ethernet, WLAN or 2G / 3G / 4G connectivity. On a closed site where key-switch release is enough, the AC MAX Basic fits; the Basic has no OCPP.

Power level and grid supply

The 16 A version delivers 3.7 kW on a single-phase connection and 11 kW on three-phase; the 32 A version delivers 7.4 kW and 22 kW respectively. The site's available current and the number of charge points determine the choice.

Cable or socket

Both current ratings are available with a 5 m Type 2 cable. Type 2 socket and socket-with-shutter versions exist only in the 32 A range; with a socket, drivers use their own charging cable.

Energy management and load balancing

With several charge points, the dynamic load management (DLM / load balancing) approach is defined in the project. The interface documented by the manufacturer is Modbus to an external energy management system: Modbus TCP on the AC MAX Smart and Modbus RTU (RS485) on the AC MAX Basic. Load management through the CPMS is only an option for the OCPP-capable AC MAX Smart, after the charger, firmware and CPMS compatibility has been confirmed for the project. The max charging current can be limited at installation with an 8-step DIP switch.

Related services and products

Energom Electronic Kft. is an official distributor of Delta Electronics. Energom assesses the site's grid supply, sizes the number and power of charge points, installs and commissions AC MAX chargers, sets up the CPMS or energy management connection, and carries out maintenance. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

Can the Delta AC MAX connect to a CPMS?

The AC MAX Smart connects to a charge point management system via OCPP 1.6, tested with OCTT, over Ethernet, WLAN or a 2G / 3G / 4G cellular link. The AC MAX Basic has no OCPP; it integrates with an energy management system over Modbus RTU (RS485).

Can the Delta AC MAX be installed on a single-phase supply?

Yes: on a single-phase connection (L1, N, PE) the Delta AC MAX 16 A version delivers 3.7 kW and the 32 A version 7.4 kW; on three-phase the rated power is 11 kW and 22 kW respectively.

Is the Delta AC MAX suitable for outdoor installation?

Yes: the Delta AC MAX is rated IP55 (IEC 60529) and IK09 (IEC 62262), operates from −30 °C to +50 °C and is cooled by natural convection.

How is the charging current of the Delta AC MAX limited?

The Delta AC MAX max charging current is set at installation with an 8-step DIP switch. In operation, the charger integrates with an energy management system over Modbus TCP (Smart) or Modbus RTU over RS485 (Basic).

Can the Delta AC MAX Basic be wall-mounted?

Yes: the manufacturer offers the Delta AC MAX Basic for wall mounting or on an optional pedestal; the unit measures 218 × 371 × 167 mm and weighs 6.0 kg including the charging cable, depending on configuration.

Request a quote

For a quote, tell us the site's grid connection (number of phases, available current), the planned number of charge points, whether you need a cable or socket version, and whether a CPMS (OCPP) or energy management integration is required.

Request a Quote

We respond within 24 hours on business days.

Request a Callback