Key specifications at a glance

  • Technology: OPzS: vented, flooded, tubular plate; not VRLA
  • Nominal rating: 2 V; 108–3,500 Ah (C10, 1.80 V/cell, 20 °C)
  • Design life: 20 years
  • Terminal: M10 female
  • Standards: DIN 40736-1, IEC 60896-11
  • Container: transparent SAN (styrene acrylonitrile)

Design life is the manufacturer's design value, not a guaranteed service life: FIAMM recommends an operating temperature of 10–30 °C, and expected life decreases above 20 °C.

Applications

  • Telecom: backup power for DC telecom power plants.
  • Industrial UPS.
  • Utilities and industry: DC auxiliary and backup power.
  • Rail: DC backup power.
  • Oil and gas.

FIAMM LM models

All models are 2 V cells; capacity is rated at C10 discharge to 1.80 V/cell at 20 °C. Dimensions follow the column order of the manufacturer's brochure: length × width × height. Weights include electrolyte.

FIAMM LM models
Model Nominal capacity DIN 40736 reference Dimensions (mm) Typical weight Electrolyte
LM 100 108 Ah 2 OPzS 100 103 × 206 × 420 14.1 kg 4.2 L
LM 150 162 Ah 3 OPzS 150 103 × 206 × 420 15.8 kg 3.8 L
LM 200 216 Ah 4 OPzS 200 103 × 206 × 420 17.4 kg 3.6 L
LM 250 270 Ah 5 OPzS 250 124 × 206 × 420 21.2 kg 4.7 L
LM 300 324 Ah 6 OPzS 300 145 × 206 × 420 24.8 kg 5.4 L
LM 350 390 Ah 5 OPzS 350 124 × 206 × 536 28.4 kg 6.3 L
LM 420 468 Ah 6 OPzS 420 145 × 206 × 536 32.7 kg 7.2 L
LM 490 546 Ah 7 OPzS 490 166 × 206 × 536 37.6 kg 8.3 L
LM 600 630 Ah 6 OPzS 600 145 × 206 × 711 44.9 kg 12.2 L
LM 700 735 Ah 7 OPzS 700 210 × 191 × 711 58.8 kg 15.0 L
LM 800 840 Ah 8 OPzS 800 210 × 191 × 711 62.2 kg 12.9 L
LM 900 945 Ah 9 OPzS 900 210 × 233 × 711 71.5 kg 22.0 L
LM 1000 1,050 Ah 10 OPzS 1000 210 × 233 × 711 74.9 kg 17.7 L
LM 1200 1,260 Ah 12 OPzS 1200 210 × 275 × 711 89.2 kg 22.1 L
LM 1500 1,570 Ah 12 OPzS 1500 210 × 275 × 861 110 kg 26.7 L
LM 1750 1,840 Ah 14 OPzS 1750 212 × 399 × 837 142 kg 35.5 L
LM 1875 1,970 Ah 15 OPzS 1875 212 × 399 × 837 147 kg 34.0 L
LM 2000 2,100 Ah 16 OPzS 2000 212 × 399 × 837 151 kg 38.3 L
LM 2250 2,360 Ah 18 OPzS 2250 212 × 487 × 837 181 kg 43.6 L
LM 2500 2,620 Ah 20 OPzS 2500 212 × 487 × 837 188 kg 48.4 L
LM 3000 3,150 Ah 24 OPzS 3000 212 × 576 × 837 222 kg 52.6 L
LM 3500 3,500 Ah 28 OPzS 3500 212 × 576 × 837 241 kg 55.2 L

Except for the LM 3500, every model's nominal capacity exceeds its DIN 40736 reference value (for example, LM 100: 108 Ah); the LM 3500 is rated at 3,500 Ah.

OPzS battery specifications

OPzS battery specifications
Parameter Value
Cell voltage 2 V
Technology vented, flooded OPzS; not VRLA
Positive plate tubular, die-cast, low-antimony alloy; very low water consumption
Separator microporous PVC
Electrolyte density 1.24 kg/L at 20 °C (1.23–1.25 kg/L in a charged cell)
Vent plugs ceramic-insert vent plugs designed by FIAMM to help prevent explosions; bayonet or screw fitting. They do not replace room ventilation.
Terminal M10 female; tightening torque 20–25 Nm
Recommended float voltage 2.23 V/cell at 20 °C
Temperature compensation not required within 20 °C ±10 °C; below 10 °C +2.5 mV/cell/°C, above 30 °C −2.5 mV/cell/°C
Typical float current approx. 0.3 mA/Ah (fully charged cell, 2.23 V/cell, 20 °C)
Boost charge after discharge 2.40 V/cell, with current limited to max 0.15 C10; stop at 0.001 C10 charge current or after 24 hours
Recommended operating temperature 10–30 °C; operable between −20 and +50 °C, with reduced expected life above 20 °C
End-of-life criterion capacity falls below 80% of nominal
Storage time without recharge 9 months at 10 °C; 5 months at 20 °C; 3 months at 30 °C (down to 80% capacity)
Container transparent SAN (styrene acrylonitrile)
Standards (brochure) DIN 40736, IEC 60896-11, DIN 43539 T5, DIN 40740 (electrolyte level indicator)
Applicable standards (engineering manual) IEC 60896-11, EN 62485-2, DIN 40736-1
Recyclability fully recyclable at end of life

Source: FIAMM LM product brochure, Rev. 11.2025; FIAMM Flooded engineering manual, Edition 07/2026, Rev.15. Specifications are subject to change by the manufacturer.

How to choose

  • Capacity and backup time: the 22 models cover a C10 capacity range from 108 Ah to 3,500 Ah. The model designation follows the DIN 40736 reference capacity; the actual nominal capacity is listed in the model table.
  • Footprint and floor loading: cell height ranges from 420 mm to 861 mm and weight, including electrolyte, from 14.1 kg to 241 kg. The LM 1750 and all larger models share an 837 mm height.
  • Charger and temperature: the rectifier must be set to a float voltage of 2.23 V/cell (20 °C); no compensation is needed between 10 and 30 °C; outside this range FIAMM's formula can be applied (+2.5 mV/cell/°C below 10 °C, −2.5 mV/cell/°C above 30 °C). FIAMM recommends an operating temperature of 10–30 °C; battery life is best at around 20 °C and decreases above it.
  • Battery room: vented OPzS cells release gas (hydrogen) during charging, so room ventilation must be designed to EN 62485-2, the standard referenced in the manufacturer's manual.
  • Operation: the transparent container and MIN/MAX level marks (DIN 40740) allow visual electrolyte level checks; FIAMM recommends a visual inspection and electrolyte level check every three months, so plan for periodic electrolyte level checks and topping up with distilled water.

Related services and products

Energom Electronic Kft. is an official distributor of FIAMM. Energom sizes LM battery banks, matches the cell count to the rectifier settings, and handles installation, commissioning and periodic maintenance. Services across the Central and Eastern European region; product delivery across Europe.

FAQ

Are OPzS batteries maintenance-free?

No. The FIAMM LM is a vented, flooded OPzS cell, not a valve-regulated (VRLA) design. FIAMM recommends a visual inspection and electrolyte level check every three months, and the electrolyte level is restored by topping up with distilled water.

What float voltage do LM OPzS cells need?

For FIAMM LM cells, FIAMM recommends a float voltage of 2.23 V/cell at 20 °C. No compensation is needed between 10 and 30 °C; a correction of +2.5 mV/cell/°C below 10 °C and −2.5 mV/cell/°C above 30 °C can be applied. A fully charged cell draws a typical float current of approx. 0.3 mA/Ah.

Which FIAMM LM model corresponds to a 10 OPzS 1000 cell?

Per the manufacturer's model table, the LM 1000 corresponds to the DIN 40736 designation 10 OPzS 1000, with a nominal capacity of 1,050 Ah (C10, 1.80 V/cell, 20 °C). Except for the LM 3500, every LM model exceeds its DIN reference capacity.

How long can LM cells be stored without recharging?

According to the manufacturer's manual, FIAMM LM cells can be stored without recharging, down to 80% capacity, for 9 months at 10 °C, 5 months at 20 °C and 3 months at 30 °C.

Request a quote

When requesting a quote, include the nominal DC system voltage, the load current, the required backup time, and the battery room dimensions and operating temperature.

Request a Quote

We respond within 24 hours on business days.

Request a Callback