Key specifications at a glance

  • Rated AC power: 1600 / 1800 / 2000 VA; 230/400 V, three-phase
  • DC input: max 65 V; 2 MPPTs, 2 inputs per MPPT (4 modules); MPPT range 16–60 V; 4 × 14–16 A
  • Efficiency: peak efficiency 96.5% (stated as CEC peak efficiency on the datasheet)
  • Grid compliance: VDE-AR-N 4105:2018, EN 50549-1:2019
  • Protection rating: IP67
  • Models: HMT-1600-4T, HMT-1800-4T, HMT-2000-4T

Applications

  • Commercial and industrial rooftop solar PV systems with a three-phase (230/400 V) grid connection.
  • Installations that require module-level monitoring and remote O&M through S-Miles Cloud.
  • Rooftop arrays built with 182 mm and 210 mm cell PV modules, with one 4-in-1 microinverter serving four modules.

HMT-4T microinverter models

HMT-4T microinverter models
Model Rated output power Key differentiator
HMT-1600-4T 1600 VA max 14 A per input; commonly used module power 320–540+ W
HMT-1800-4T 1800 VA max 15 A per input; commonly used module power 360–600+ W
HMT-2000-4T 2000 VA max 16 A per input; commonly used module power 400–670+ W

Hoymiles HMT-4T microinverter specifications

Hoymiles HMT-4T microinverter specifications
Parameter Value
Rated output power 1600 / 1800 / 2000 VA (HMT-1600-4T / HMT-1800-4T / HMT-2000-4T)
Rated output current 3 × 2.32 A (HMT-1600-4T); 3 × 2.61 A (HMT-1800-4T); 3 × 2.9 A (HMT-2000-4T)
Grid connection 230/400 V, 3W+N+PE; 50 Hz
Power factor > 0.99 (default; adjustable)
Total harmonic distortion < 3%
Max DC input voltage 65 V
MPPT voltage range 16–60 V
Start-up voltage (min / max) 22 V / 60 V
MPPTs and inputs 2 MPPTs, 2 inputs per MPPT (4 PV modules)
Max input current 4 × 14 A (HMT-1600-4T); 4 × 15 A (HMT-1800-4T); 4 × 16 A (HMT-2000-4T)
Max input short-circuit current 4 × 25 A
Commonly used module power 320–540+ W (HMT-1600-4T); 360–600+ W (HMT-1800-4T); 400–670+ W (HMT-2000-4T)
Compatible modules PV modules with 182 mm and 210 mm cells
Peak efficiency 96.5% (stated as CEC peak efficiency); the datasheet does not state a European weighted efficiency
Nominal MPPT efficiency 99.8%
Night-time power consumption < 50 mW
Isolation galvanically isolated HF transformer
Grid protection integrated grid protection relay
Cooling natural convection, no fans
Protection rating IP67
Ambient temperature range −40 to +65 °C
Storage temperature range −40 to +85 °C
Dimensions (W × H × D) 326 × 222 × 40.6 mm
Weight 5.9 kg
Communication, monitoring Sub-1G wireless link to the Hoymiles DTU gateway; module-level monitoring in S-Miles Cloud
Grid compliance VDE-AR-N 4105:2018; EN 50549-1:2019; VFR 2019
Safety, EMC IEC/EN 62109-1/-2; IEC/EN 61000-6-1/-2/-3/-4; IEC/EN 61000-3-2/-3

Source: Hoymiles microinverter datasheet (EMEA & APAC region), V202302; Hoymiles EU product page, November 2026. Specifications are subject to change by the manufacturer.

How to choose

Module power and model

Start from the power and current of the PV modules you plan to connect. The datasheet lists these commonly used module power ranges:

How to choose
PV module Suggested model Why
320–540+ W HMT-1600-4T max 14 A per input, 1600 VA output
360–600+ W HMT-1800-4T max 15 A per input, 1800 VA output
400–670+ W HMT-2000-4T max 16 A per input, 2000 VA output

DC-side matching

  • The module operating current should fit the max input current of 14, 15 or 16 A per input; max input short-circuit current is 4 × 25 A.
  • The module MPP voltage should sit within the 16–60 V MPPT range, and its open-circuit voltage at the lowest expected temperature must not exceed the 65 V max DC input voltage; start-up voltage is 22 V.

Grid connection and monitoring

  • The microinverter output is three-phase (230/400 V, 3W+N+PE, 50 Hz), with grid compliance to VDE-AR-N 4105:2018 and EN 50549-1:2019.
  • Sub-1G communication runs through the Hoymiles DTU gateway, so the DTU needs a place in the system design for module-level monitoring.
  • For outdoor rooftop locations, the relevant data points are IP67 protection, the −40 to +65 °C ambient range and fanless cooling.

Related services and products

Energom Electronic Kft. is an official distributor of Hoymiles. Services across the Central and Eastern European region; product delivery across Europe. Energom handles microinverter PV system sizing, module-to-inverter matching checks, installation, commissioning and monitoring setup.

FAQ

How many PV modules can one Hoymiles HMT-4T microinverter handle?

The HMT-1600-4T, HMT-1800-4T and HMT-2000-4T each have two MPPTs with two inputs per MPPT; max input current is 14, 15 or 16 A per input depending on the model.

Which grid standards does the Hoymiles HMT-4T meet?

According to the datasheet, the Hoymiles HMT-4T complies with VDE-AR-N 4105:2018, EN 50549-1:2019 and VFR 2019; the listed safety standard is IEC/EN 62109-1/-2.

Does the Hoymiles HMT-4T require a DTU gateway?

The DTU is needed for module-level monitoring: HMT-4T microinverters communicate with the Hoymiles DTU gateway over a Sub-1G wireless link, and module-level data is available in S-Miles Cloud, so the DTU needs a place in the system design.

Request a quote

When requesting a quote, include the PV module type, power and quantity, the roof layout, grid connection details and your monitoring requirements.

Request a Quote

We respond within 24 hours on business days.

Request a Callback