Hoymiles HoyUltra 261A 99.9–125 kW / 261 kWh All-in-One C&I BESS
The Hoymiles HoyUltra 261A (HESS-261-2h) is a 125 kW (rated at 50 °C) / 261 kWh all-in-one C&I battery energy storage system (BESS) cabinet in which liquid cooling serves both the power conversion system and the LFP battery. Applications include peak shaving, self-consumption optimization and backup power at commercial and industrial sites. Hoymiles specifies up to 90.3% round-trip efficiency, and up to 16 units can be paralleled on-grid.
Key specifications at a glance
- Power, energy: 125 kW rated (at 50 °C), max 137.5 kVA (HESS-261-2h; the (124) and (99) versions 124.9 and 99.9 kW); 261 kWh; 340–440 V AC
- Cells, cooling: LFP; fully liquid cooling (PCS + battery)
- Overload capability: HESS-261-2h (standard version): 1.1× long-term (137.5 kVA at 50 °C) and 1.2× for at least 1 minute; overload data for the (124) and (99) versions is confirmed when quoting
- Round-trip efficiency: max 90.3%
- Parallel capability: max 16 units grid-connected, max 8 units off-grid
- Compliance, protection rating: EN 50549-1/-2/-10, VDE-AR-N 4105 / 4110; IEC 62619, IEC 63056; IP55
Applications
- Peak shaving and valley filling under time-of-use tariffs.
- Demand charge management.
- PV self-consumption optimization and export limitation (anti-reverse current).
- Off-grid and backup power supply.
- Virtual power plant (VPP) and electricity market participation.
- Noise-sensitive sites such as supermarkets, hotels and residential areas, with the 60 dB option.
HoyUltra 261A versions: all-in-one energy storage cabinets
| Model | Rating | Key feature |
|---|---|---|
| HESS-261-2h | 125 kW / 261 kWh | standard version: max 137.5 kVA, 100 kW off-grid |
| HESS-261-2h(124) | 124.9 kW / 261 kWh | on-grid output limited to 124.9 kVA |
| HESS-261-2h(99) | 99.9 kW / 261 kWh | on-grid output limited to 99.9 kVA |
All three versions share the same 261 kWh battery system and cabinet; they differ in the on-grid output power limit.
C&I battery storage specifications
| Parameter | Value |
|---|---|
| Rated energy | 261 kWh |
| On-grid rated power at 50 °C | 125 kW (HESS-261-2h); 124.9 kW (HESS-261-2h(124)); 99.9 kW (HESS-261-2h(99)) |
| Max apparent power at 50 °C | 137.5 kVA (HESS-261-2h); 124.9 kVA (HESS-261-2h(124)); 99.9 kVA (HESS-261-2h(99)) |
| Off-grid rated power at 50 °C | 100 kW (HESS-261-2h); 99.92 kW (HESS-261-2h(124)); 99.9 kW (HESS-261-2h(99)) |
| AC voltage range | 340–440 V AC |
| Grid frequency, connection | 50 Hz or 60 Hz, ±5 Hz; 3/N or 3/N/PE |
| Current harmonic distortion (THDi), short-circuit current | <3% at rated power; Icc 10 kA |
| Off-grid voltage quality | THDu <3% at linear load; DC injection <1% Un at balanced linear load |
| Off-grid unbalance | 100% three-phase unbalanced load in off-grid parallel mode |
| Overload capability | HESS-261-2h (standard version): 1.1× long-term (137.5 kVA at 50 °C) and 1.2× for at least 1 minute; overload data for the (124) and (99) versions is confirmed when quoting. The (124) and (99) versions are limited to 124.9 kVA and 99.9 kVA max apparent power. |
| Round-trip efficiency | max 90.3% |
| Cells, configuration | LFP; pack 1P52S / 52.25 kWh; system 1P260S |
| DC voltage range | 728–936 V DC |
| Temperature sensing | battery cell, module, positive and negative terminals |
| Rated charge and discharge rate | ≤0.5P |
| Cooling | full liquid cooling (PCS and battery) |
| Parallel capability | max 16 units grid-connected, max 8 units off-grid |
| Scalability | on-grid from 125 kW / 261 kWh up to 2 MW / 4 MWh (16 units); off-grid max 8 units |
| Grid functions | PQ and VF control, black start |
| Communication | RS485, Ethernet, DIO; Modbus RTU, Modbus TCP, DL/T645; S-Miles Cloud service, third-party cloud platforms supported |
| Dimensions (W × H × D), weight | 1,030 × 2,450 × 1,400 mm; <2,800 kg |
| Protection rating | IP55 |
| Operating environment | −30 to +55 °C; 0–100% RH, non-condensing; max 2,000 m |
| Noise level | 70 dB, optionally 60 dB (measurement conditions not stated by the manufacturer) |
| Fire suppression | aerosol, water fire protection, interlocked exhaust ventilation, pressure relief (optional) |
| AC cable entry | front bottom inlet |
| Grid code compliance | EN 50549-1/-2/-10, VDE-AR-N 4105 / 4110 / 4120, DIN VDE V 0124-100, CEI 0-21, CEI 0-16, NC RfG (2016/631/EU), G99, PSE 2018, RD244, UNE 217001:2020 |
| Product compliance | IEC 62619, IEC 63056, EN/IEC 62477-1:2012, EN IEC 61000-6-2 and 61000-6-4:2019, UN 38.3 Rev.8, IEC 60730-1 Annex H, IEC 61683, EN/IEC 62920 |
Source: Hoymiles HoyUltra 261A datasheet, Global REV2.1, 2026; HESS-261-2h user manual, REV1.1, July 2025 (parallel operation, scalability, operating modes); Hoymiles EU product page, November 2026 (grid functions). Specifications are subject to change by the manufacturer.
How to choose
Version by grid connection
The standard version delivers 125 kW rated and up to 137.5 kVA apparent power at 50 °C. If the connection agreement or grid code limits the export capacity, the HESS-261-2h(124) or HESS-261-2h(99) version, limited to 124.9 kVA or 99.9 kVA respectively, can be selected. All three versions store 261 kWh.
Scaling through parallel operation
Up to 16 units can be paralleled on-grid and up to 8 off-grid. According to the Hoymiles user manual, the system scales on-grid from 125 kW / 261 kWh up to 2 MW / 4 MWh.
Operating mode and energy management
The user manual describes peak shaving and valley filling, demand charge management, export limitation, off-grid and backup power, and remote-controlled (VPP) operation. Choose the target function based on the site load profile and tariff structure.
Off-grid and backup operation
Off-grid, the standard version delivers 100 kW rated at 50 °C with THDu <3% at linear load, and handles 100% three-phase unbalanced load in off-grid parallel mode. Hoymiles also lists black start capability.
Installation environment
The IP55-rated cabinet operates from −30 to +55 °C, with rated power specified at 50 °C. For noise-sensitive sites, the 60 dB option is available (standard: 70 dB). Plan the foundation and cable routing in advance for the <2,800 kg weight and the front bottom AC inlet.
Related services and products
- C&I energy storage
- Industrial energy management – coordinating generation, storage and consumption
- Design and installation – sizing, installation and commissioning
- Monitoring and optimization – monitoring and operational support
- Hoymiles HoyUltra 128D hybrid energy storage
- Hoymiles HoyUltra 2000M containerized energy storage
Energom Electronic Kft. is an official distributor of Hoymiles. Services across the Central and Eastern European region; product delivery across Europe. Energom sizes HoyUltra 261A systems based on the site load profile, the connection conditions and the target function, including the choice of version and number of units, and also handles installation, commissioning and maintenance.
FAQ
Can the HoyUltra 261A be paralleled?
The HoyUltra 261A can be paralleled: up to 16 units on-grid and up to 8 off-grid. According to the Hoymiles user manual, this lets the system scale on-grid from 125 kW / 261 kWh up to 2 MW / 4 MWh.
What is the difference between the HESS-261-2h, HESS-261-2h(124) and HESS-261-2h(99)?
The Hoymiles HoyUltra 261A versions differ mainly in on-grid output power: the standard version is rated at 125 kW and up to 137.5 kVA, while the (124) version is limited to 124.9 kVA and the (99) version to 99.9 kVA, all at 50 °C. The off-grid rated power also differs slightly: 100 kW, 99.92 kW and 99.9 kW respectively (at 50 °C). All three versions store 261 kWh.
Can the HoyUltra 261A operate off-grid?
In off-grid operation, the standard Hoymiles HoyUltra 261A version is rated at 100 kW at 50 °C and handles 100% three-phase unbalanced load in off-grid parallel mode. Hoymiles also lists black start capability.
How loud is the HoyUltra 261A?
Hoymiles specifies 70 dB, with an optional 60 dB version recommended for supermarkets, hotels and residential areas. The datasheet does not state the measurement conditions.
Which grid codes does the HoyUltra 261A comply with?
According to the datasheet, the Hoymiles HoyUltra 261A complies with grid codes including EN 50549-1/-2/-10, VDE-AR-N 4105, 4110 and 4120, and NC RfG (2016/631/EU), and at product level with IEC 62619 and IEC 63056.
Request a quote
When requesting a quote, please include the site load profile or monthly peak demand, the grid connection capacity, the target function (peak shaving, self-consumption, backup power), PV system details and the installation site conditions.
We respond within 24 hours on business days.