Hoymiles HoyUltra 2000M 1–1.25 MW Containerized C&I BESS
The Hoymiles HoyUltra 2000M (HESS-2088-2h, HESS-2610-2h) is a containerized, MWh-scale C&I battery energy storage system (BESS) with 1 or 1.25 MW AC power (combined PCS rating at 50 °C) and 2.088 or 2.61 MWh of energy. The LFP battery, BMS, power conversion system (PCS), optional static transfer switch (STS), thermal management and fire protection are integrated in one liquid-cooled container. Applications include peak shaving, PV self-consumption and backup power.
Key specifications at a glance
- Power, energy: 1 MW / 2.088 MWh (HESS-2088-2h); 1.25 MW / 2.61 MWh (HESS-2610-2h); MW figure = combined PCS AC power at 50 °C
- Cells, cooling: LFP, 314 Ah; liquid cooling
- Round-trip efficiency: max 91%
- Compliance, protection rating: EN 50549-1/-2/-10; IP55
Applications
- Time-of-use operation and peak-valley arbitrage.
- PV self-consumption.
- Peak shaving.
- Backup power for critical loads.
- Virtual power plant (VPP) aggregation.
- Commercial, industrial and grid-scale energy storage.
HoyUltra 2000M models: containerized energy storage
| Model | Rating | Key feature |
|---|---|---|
| HESS-2088-2h | 1 MW / 2.088 MWh | 8 × 125 kW PCS; 8P260S; optional PV and generator circuit breakers |
| HESS-2610-2h | 1.25 MW / 2.61 MWh | 10 × 125 kW PCS; 10P260S |
The MW figure in the "Rating" column is the max AC power at 50 °C as specified by Hoymiles, i.e. the combined rating of the 125 kW power conversion modules. The datasheet also lists a separate max output power of 1.1 MW and 1.375 MW at 50 °C, without stating the operating conditions; we clarify which value applies for sizing with the manufacturer when quoting. Both models use the same container size, with 6-in-1 integration of the battery, BMS, PCS, optional static transfer switch, thermal management and fire protection.
Containerized C&I battery storage specifications
| Parameter | HESS-2088-2h | HESS-2610-2h |
|---|---|---|
| Rated energy | 2.088 MWh | 2.61 MWh |
| Max AC power (combined PCS), 50 °C | 1 MW (8 × 125 kW) | 1.25 MW (10 × 125 kW) |
| Max output power at 50 °C | 1.1 MW | 1.375 MW |
| Rated AC current | 1,444 A | 1,805 A |
| Grid voltage | 400 V AC (340–440 V); 3L + N + PE | 400 V AC (340–440 V); 3L + N + PE |
| Grid frequency | 50 Hz or 60 Hz (operating range 45–55 Hz or 55–65 Hz) | 50 Hz or 60 Hz (operating range 45–55 Hz or 55–65 Hz) |
| Total harmonic distortion | <3% at rated power | <3% at rated power |
| Cells, pack | LFP, 3.2 V / 314 Ah; pack 1P52S | LFP, 3.2 V / 314 Ah; pack 1P52S |
| System configuration | 8P260S | 10P260S |
| Rated DC voltage | 832 V | 832 V |
| Rated charge and discharge rate | 0.5P | 0.5P |
| Round-trip efficiency | max 91% | max 91% |
| Cooling | liquid cooling | liquid cooling |
| On-grid and off-grid transfer | optional built-in static transfer switch (STS), <20 ms | optional built-in static transfer switch (STS), <20 ms |
| Grid forming | black start and grid-forming operation | black start and grid-forming operation |
| Optional circuit breakers | PV breaker 2,500 A, generator breaker 2,000 A | no value given in the datasheet |
| Dimensions (L × W × H) | 6,058 × 2,431 × 2,591 mm | 6,058 × 2,431 × 2,591 mm |
| Weight | 27.5 t | 28 t |
| Operating temperature | −30 to +55 °C, derating above 50 °C | −30 to +55 °C, derating above 50 °C |
| Humidity, altitude | 0–95%, non-condensing; derating from 2,000 m | 0–95%, non-condensing; derating from 2,000 m |
| Protection rating, corrosion class | IP55; C4, optionally C5 | IP55; C4, optionally C5 |
| Noise level | <75 dB (measurement conditions not stated by the manufacturer) | <75 dB (measurement conditions not stated by the manufacturer) |
| Fire suppression | combustible gas, smoke and temperature detectors; compartment-level aerosol suppression; water fire suppression; integrated ventilation | combustible gas, smoke and temperature detectors; compartment-level aerosol suppression; water fire suppression; integrated ventilation |
| Communication | CAN, RS485, Ethernet; Modbus TCP, MQTT | CAN, RS485, Ethernet; Modbus TCP, MQTT |
| Compliance | EN 50549-1/-2/-10, IEC 60730, IEC 62619, IEC 62477, IEC 61000, IEC 62116, VDE-AR-N 4105, C10/C11, NC RfG (2016/631/EU), PSE 2018-12-18 | EN 50549-1/-2/-10, IEC 60730, IEC 62619, IEC 62477, IEC 61000, IEC 62116, VDE-AR-N 4105, C10/C11, NC RfG (2016/631/EU), PSE 2018-12-18 |
Source: Hoymiles HoyUltra 2000M datasheet, Global REV V0.9, 2026. Specifications are subject to change by the manufacturer.
How to choose
Power and energy
The HESS-2088-2h is built with eight and the HESS-2610-2h with ten 125 kW power conversion modules, giving 1 MW and 1.25 MW max AC power at 50 °C and 2.088 MWh and 2.61 MWh of energy respectively. Both models have a 0.5P rated charge and discharge rate. Model selection starts from the site load profile and the target function.
PV and generator integration
Hoymiles specifies optional PV inverter and generator integration ports, managed through the energy management system (EMS). The datasheet lists an optional PV circuit breaker (2,500 A) and generator circuit breaker (2,000 A) for the HESS-2088-2h only.
Off-grid and backup operation
The optional built-in static transfer switch (STS) transfers between on-grid and off-grid operation in under 20 ms. Hoymiles specifies black start and grid-forming operation, supporting critical loads during grid outages.
Expanding with multiple containers
Multiple containers can be connected in parallel. The datasheet does not state the maximum number of containers, so larger systems are configured through project-specific sizing.
Installation and environment
The container measures 6,058 × 2,431 × 2,591 mm and weighs 27.5 t or 28 t, so transport, lifting and foundation work need advance planning. The operating range is −30 to +55 °C with derating above 50 °C; the corrosion class is C4, optionally C5, and the noise level is below 75 dB.
Related services and products
- C&I energy storage
- Industrial energy management – coordinating generation, storage and consumption
- Design and installation – sizing, installation and commissioning
- Monitoring and optimization – monitoring and operational support
- Hoymiles HoyUltra 128D hybrid energy storage
- Hoymiles HoyUltra 261A energy storage
Energom Electronic Kft. is an official distributor of Hoymiles. Services across the Central and Eastern European region; product delivery across Europe. Energom sizes HoyUltra 2000M systems based on the site load profile, the grid connection conditions, PV and generator integration and the target function, and also handles installation, commissioning and maintenance.
FAQ
What is the power rating of the HoyUltra 2000M?
According to the Hoymiles datasheet, max AC power at 50 °C is 1 MW for the HESS-2088-2h (eight 125 kW power conversion modules) and 1.25 MW for the HESS-2610-2h (ten modules). The datasheet also lists a separate max output power of 1.1 MW and 1.375 MW at 50 °C, without stating the operating conditions; we clarify which value applies for sizing with the manufacturer when quoting.
What is the difference between the HESS-2088-2h and the HESS-2610-2h?
The Hoymiles HoyUltra 2000M HESS-2088-2h offers 1 MW max AC power at 50 °C, 2.088 MWh of energy and an 8P260S configuration; the datasheet lists an optional PV circuit breaker (2,500 A) and generator circuit breaker (2,000 A) for this model. The HESS-2610-2h offers 1.25 MW, 2.61 MWh and a 10P260S configuration. Both use the same container size.
Does the HoyUltra 2000M support off-grid operation and black start?
Hoymiles specifies black start and grid-forming operation; the optional built-in static transfer switch (STS) transfers between on-grid and off-grid operation in under 20 ms.
Can multiple HoyUltra 2000M containers be paralleled?
Yes, Hoymiles specifies multi-cabinet parallel connection. The number of containers and the configuration are determined during project sizing.
Which communication interfaces does the HoyUltra 2000M offer?
The Hoymiles HoyUltra 2000M communicates over CAN, RS485 and Ethernet interfaces, using Modbus TCP and MQTT protocols. Hoymiles also lists virtual power plant (VPP) aggregation and multiple EMS operating modes.
Request a quote
When requesting a quote, please include the site load profile, the grid connection capacity, the target function (peak shaving, PV self-consumption, backup power, arbitrage), existing or planned PV and generator capacity, and the installation site conditions.
We respond within 24 hours on business days.