Key specifications at a glance

  • Connection: single-phase, direct, 5(45) A; 230 V
  • Accuracy class: Class C or B (EN 50470-3:2022); Class 0.5 or 1 (IEC 62053-21)
  • MID: module B+D, certificate number 0120/SGS0141 according to the datasheet; the MID-certified version is confirmed with the quote
  • Communication: RS485 Modbus RTU (SDM120-M), M-Bus (SDM120-MB), pulse only (SDM120-P); 2 pulse outputs
  • Measured quantities: bidirectional kW and kWh; kvarh, var, VA, V, A, PF, Hz, demand
  • Width: 1 DIN module (18 mm)

Applications

  • Solar PV energy metering with bidirectional (import and export) measurement
  • Energy metering for EV charging systems
  • Industrial and utility applications
  • Residential submetering

Eastron SDM120 models

All three models share the same electrical ratings; they differ in the communication interface.

Eastron SDM120 models
Model Rating Distinguishing feature
SDM120-M single-phase, 5(45) A, 230 V RS485 Modbus RTU
SDM120-MB single-phase, 5(45) A, 230 V M-Bus (EN 13757-3)
SDM120-P single-phase, 5(45) A, 230 V pulse output only

Technical specifications – single-phase DIN rail energy meter

Technical specifications – single-phase DIN rail energy meter
Parameter Value
Connection single-phase, direct
Nominal voltage 230 V
Operating voltage range 85–276 V AC
Frequency 50/60 Hz
Current 5(45) A
Minimum current (Imin) 0.15 A
Starting current 20 mA (0.4% Ib)
Overcurrent withstand 30 × Imax for 0.01 s
Active energy accuracy Class C or B (EN 50470-3:2022); Class 0.5 or 1 (IEC 62053-21)
Reactive energy accuracy Class 2 (IEC 62053-23)
Accuracy of instantaneous values voltage ±0.5% (of range maximum), current ±0.5% (of nominal), frequency ±0.2%, power factor ±1%, active, reactive and apparent power ±1% (of range maximum)
Internal power consumption ≤ 2 W / 10 VA
Insulation 4 kV AC for 1 minute; impulse 6 kV (1.2 µs)
Pulse outputs 2 passive outputs; output 2 fixed at 1,000 imp/kWh; output 1 configurable (total, import or export kWh or kvarh; 0.001, 0.01, 0.1 or 1 kWh per pulse); pulse width 200, 100 or 60 ms
RS485 Modbus RTU – SDM120-M 2,400–38,400 bps; address 1–247; max 64 devices per bus; max 1,000 m; response time < 100 ms
M-Bus – SDM120-MB EN 13757-3; 300–9,600 bps; primary address 1–250; secondary address 00 00 00 01–99 99 99 99
Display backlit LCD
Operating temperature SDM120-M manual (2025): −40 to +70 °C; series datasheet (2024): −25 to +55 °C
Storage temperature SDM120-M manual (2025): −40 to +80 °C; series datasheet (2024): −40 to +70 °C
Relative humidity SDM120-M: 0–95%, non-condensing; SDM120-MB and SDM120-P: operating ≤ 90%, storage ≤ 95%, non-condensing
Ingress protection IP51 (indoor)
Installation environment installation category CAT III; protective class II; mechanical environment M1, electromagnetic environment E2; pollution degree 2; altitude max 2,000 m
Dimensions (W × H × D) 18 × 118 × 64 mm (DIN 43880); 35 mm DIN rail
Wire size – SDM120-M main terminals 2.5–10 mm², M4, 1.5 Nm; signal terminals 0.5–1.5 mm², M2.5, 0.2 Nm
Compliance EMC: EN 61326-1:2013, EN 61326-2-3:2013; Low Voltage Directive: EN 61010-1:2010+A1:2019, EN 61010-2-030:2010; MID: 2014/32/EU

Source: Eastron SDM120 series datasheet (August 2024), SDM120-M user manual (V1.0, March 2025) and manufacturer product page (as of November 2026). Specifications are subject to change by the manufacturer.

How to choose

Communication and system integration

For a monitoring platform, an energy management system (EMS) or a building management system, the SDM120-M connects over RS485 Modbus RTU, with up to 64 devices per bus and cable runs up to 1,000 m. The SDM120-MB fits M-Bus meter reading networks. Where pulse counting is enough, the SDM120-P is the simplest version. All three models have 2 pulse outputs.

Current and connection

The SDM120 is a direct-connected single-phase meter rated 5(45) A. Circuits carrying more than 45 A need a CT-connected meter; for three-phase feeders, the Eastron SDM630 (direct connection up to 100 A) or the CT-connected SDM630MCT are the options to consider.

Bidirectional metering for solar PV and EV charging

The meter registers imported and exported energy separately. Pulse output 1 can be set to total, import or export energy, so the two directions can also be passed on separately in a PV system.

MID-certified metering

If the application requires certified metering, for example because energy is billed to a third party, choose a MID-certified version. The Eastron series datasheet states conformity with the Measuring Instruments Directive (2014/32/EU), with module B+D; please indicate in your quote request if you need a MID-certified meter, and we will confirm the version and order code.

Installation environment

The meters are rated IP51 and designed for indoor distribution boards. The manufacturer documents state different operating temperature ranges (see the specifications table); for unheated or extreme-temperature locations, state the ambient conditions in your quote request.

Related services and products

Energom Electronic Kft. is an official distributor of Eastron. Services across the Central and Eastern European region; product delivery across Europe. For SDM120 projects, Energom plans the metering points and the communication network, handles installation and commissioning, and integrates the meters with your monitoring platform or energy management system.

FAQ

Does the Eastron SDM120 measure energy in both directions?

The SDM120 measures active power and energy (kW, kWh) bidirectionally and registers import and export separately, which makes it suitable for metering solar PV systems.

Which communication options are available for the SDM120?

The SDM120-M uses RS485 Modbus RTU, the SDM120-MB uses M-Bus (EN 13757-3), and the SDM120-P has pulse outputs only. Every model has 2 pulse outputs.

What is the maximum current of the Eastron SDM120?

The SDM120 is a direct-connected single-phase meter rated 5(45) A at 230 V. Its minimum current (Imin) is 0.15 A and its starting current is 20 mA.

Is the SDM120 series MID-certified?

The Eastron SDM120 series datasheet states conformity with the Measuring Instruments Directive (2014/32/EU), with module B+D (certificate number 0120/SGS0141). The MID-certified version and its order code are confirmed with the quote; active energy accuracy is Class C or B to EN 50470-3:2022.

Where can the SDM120 be installed?

The Eastron SDM120 mounts on a 35 mm DIN rail and is 1 DIN module (18 mm) wide. With an IP51 rating, it is intended for indoor distribution boards.

Request a quote

To help us prepare your quote, please include the number of metering points, the current of the metered circuits, the required communication (Modbus, M-Bus or pulse), whether MID certification is needed and the receiving monitoring or energy management system.