Key specifications at a glance

  • Output signal: 85 mV/kA at 50 Hz (Ø8 mm types: ESCT-RC60 … RC240); 50 mV/kA (Ø6 mm types: ESCT-RC16, RC24, RC36)
  • Accuracy (type A): calibrated <0.5% (central position, 25 °C); linearity ±0.2% of reading; phase error ≤0.5°; error due to conductor position max ±1%
  • Window size: 16 and 24 mm (Ø6 mm coil); 50–240 mm (Ø8 mm coil)
  • Lead: 2 m, blue (+) and black (−) wire; length customizable
  • Operating temperature: −30 to +80 °C
  • Compatible meters: Eastron SDM630MCT-RC, 85 mV/kA input (ESCT-RC60 / RC100 / RC150)

Applications

  • Current measurement on large or awkwardly shaped conductors and busbars
  • Current measurement in places with limited access
  • Measurement with portable instruments
  • Ripple current measurement in battery charging systems with a large DC component
  • Metering points where a traditional current transformer does not fit due to its size or weight

Eastron ESCT-RC Rogowski coil models

The number in the model code refers to the nominal window size; Eastron designates the coil designs as types A, B, C and D.

Eastron ESCT-RC Rogowski coil models
Model Rating Key feature
ESCT-RC16 / RC24 / RC36 50 mV/kA (50 Hz), Ø6 mm coil, type C smallest window sizes; IP54
ESCT-RC45 85 mV/kA (50 Hz), type D 45 mm window; IP68
ESCT-RC60 / RC105 / RC240 85 mV/kA (50 Hz), Ø8 mm coil, type A window size (A / B): 60 / 50, 105 / 100 and 245 / 240 mm respectively; 200 / 350 / 800 mm coil length; IP68
ESCT-RC100 / RC150 / RC200 85 mV/kA (50 Hz), Ø8 mm coil, type B ESCT-RC100: 100 mm window, 395 mm coil length; ESCT-RC150: 150 mm window, 525 mm coil length; IP68

Rogowski coil technical specifications

Rogowski coil technical specifications
Parameter Value
Measuring principle air-cored Rogowski coil; measures AC, not DC; with no iron core it does not saturate and measures the AC component accurately even with a large DC component
Rated output signal (50 Hz) 85 mV/kA: ESCT-RC45 (type D) and Ø8 mm types A and B (ESCT-RC60, RC100, RC105, RC150, RC200, RC240); 50 mV/kA: Ø6 mm type C (ESCT-RC16, RC24, RC36)
Accuracy, calibrated – type A <0.5% (central position, 25 °C)
Accuracy, uncalibrated – ESCT-RC60 / RC105 / RC240 tolerance <5% (central position, 25 °C)
Linearity – type A ±0.2% of reading
Position error – type A max ±1%
Phase error – type A ≤0.5°
Maximum measurable current – ESCT-RC60 / RC105 / RC240 100 kA
Window size (A / B) and outer diameter – type A ESCT-RC60: 60 / 50 mm, OD 66 mm; ESCT-RC105: 105 / 100 mm, OD 121 mm; ESCT-RC240: 245 / 240 mm, OD 261 mm
Coil length – type A ESCT-RC60: 200 mm; ESCT-RC105: 350 mm; ESCT-RC240: 800 mm
Window size and coil length – ESCT-RC100 / RC150 ESCT-RC100: 100 mm, 395 mm; ESCT-RC150: 150 mm, 525 mm
Coil resistance – type A ESCT-RC60: 140 Ω; ESCT-RC105: 210 Ω; ESCT-RC240: 430 Ω (each ±10 Ω)
Temperature coefficient – type A uncalibrated 200 ppm/°C; calibrated 300 ppm/°C
Zero drift – type A ≤0.05 mV (at 0 A)
Shielding fully shielded coil; rejects external magnetic fields and nearby conductors
Effect on measured circuit non-intrusive, draws no power from the measured circuit; not damaged by large overloads
Signal processing the coil signal is processed by an integrator (90° phase-shift compensation, frequency equalization); Eastron meters with Rogowski inputs (e.g. SDM630MCT-RC) accept the coils without an external integrator if the coil output matches the meter input
Lead 2 m; cable length customizable
Ordering code example: ESCT-RC60-2M-85-B = ESCT-RC60 (window size A / B: 60 / 50 mm), 2 m cable, 85 mV/kA, blue; color codes: R (red), B (blue), O (orange), Y (yellow), G (green); cable length and ratio customizable
Degree of protection IP68 (types A, B and D); IP54 (type C: ESCT-RC16, RC24, RC36)
Operating temperature – type A −30 to +80 °C
Storage temperature – type A −40 to +90 °C

Source: Eastron ESCT-RC series page and Ø8 mm model page (manufacturer product pages, retrieved November 2026), Eastron Rogowski Coils – ESCT-RC and SRC series catalog (April 2025), and ESCT-RC100 and RC150 dimensions from the Eastron SDM630MCT-RC user manual, V1.2 (April 2026). Specifications are subject to change by the manufacturer.

How to choose

Window size for the conductor

The size of the conductor or busbar drives the choice: the Ø6 mm type C (ESCT-RC16, RC24, RC36) suits smaller conductors, while the Ø8 mm types A and B, with 50–240 mm windows, are built for large conductors and busbars. The flexible, openable coil fits around the conductor without disconnecting it.

Output signal and receiving meter

The Ø6 mm models deliver a rated 50 mV/kA and all other models 85 mV/kA at 50 Hz. When ordering, match the output signal to the input of the receiving meter; the ratio can be customized.

Current range

The Ø8 mm type A models (ESCT-RC60, RC105, RC240) measure up to 100 kA. Because the Rogowski coil is air-cored, it does not saturate at high currents and large overloads do not damage it.

Accuracy in practice

A calibrated type A coil (ESCT-RC60, RC105, RC240) is accurate to <0.5% in the central position at 25 °C, with a position error of max ±1%. If the conductor does not pass through the center of the coil, factor in the position error. Uncalibrated type A coils have a tolerance of <5%.

Installation environment

Types A, B and D are rated IP68 and type C IP54; in wet or dusty locations this difference decides the choice.

Cable length and color option

The standard lead is 2 m, and the cable length can be customized. The coil can be ordered in five colors (R, B, O, Y, G), which can help tell metering points apart.

Related services and products

Energom Electronic Kft. is an official distributor of Eastron. Services across the Central and Eastern European region; product delivery across Europe. For Eastron ESCT-RC Rogowski coils, Energom selects the metering points and coil sizes, installs and commissions the coils together with the meters, and connects the metering data to your monitoring system.

FAQ

Can the Eastron ESCT-RC Rogowski coil measure DC current?

The Eastron ESCT-RC does not measure DC: a Rogowski coil measures AC only. With no iron core, however, it measures the AC component accurately even with a large DC component, so it can be used for ripple measurement in battery charging systems.

Which meters can ESCT-RC Rogowski coils connect to?

The Rogowski coil signal must be processed by an integrator; Eastron meters with Rogowski inputs (e.g. SDM630MCT-RC) do this internally, so they accept the coils without an external integrator. When ordering, match the coil output signal to the input of the receiving meter: the SDM630MCT-RC needs 85 mV/kA coils, the MID-certified SDM630MCT-RC MID needs 100 mV/kA coils; the 100 mV/kA order version is confirmed with the quote.

Is an open-circuited secondary a hazard with ESCT-RC coils?

According to Eastron, unlike traditional current transformers, the air-cored Rogowski coil poses no danger from an open-circuited secondary, and large overloads do not damage it. Safety rules for working on live conductors still apply.

Where can the ESCT-RC Rogowski coil be installed?

Types A, B and D are rated IP68, and type C (ESCT-RC16, RC24, RC36) is rated IP54.

How much current can ESCT-RC coils measure?

The Ø8 mm type A models (ESCT-RC60, RC105, RC240) measure up to 100 kA. The air-cored coil does not saturate at high currents.

Request a quote

For your quote, please include the size of the conductors or busbars, the expected maximum current, the receiving meter model (state if certified MID metering is needed), the required cable length and the installation environment.

Request a Quote

We respond within 24 hours on business days.

Request a Callback